3 How to Configure the System

3.1 Configure the DeviceNet Network

All DeviceNet stations that are connected to the same network must have a
unique station address. The DeviceNet address of the frequency converter
can be selected via:

-

Hardware switches (default 63)

-

par. DN-02 MAC ID (default 63)

-

Class code 0X03, Instance 1, Attribute 1

3.1.1 Setting the DeviceNet Address using the Hardware Switches

Setting the DeviceNet Address using the Hardware Switches: Using the hardware switches it is possible to select an address range from 0-63 (factory setting 63)
according to the table below:

Switch

8

7

6

5

4

3

2

1

Address value

-

-

+32

+16

+8

+4

+2

+1

Ex. address 5

-

-

OFF

OFF

OFF

ON

OFF

ON

Ex. address 20

-

-

OFF

ON

OFF

ON

OFF

OFF

Ex. address 35

-

-

ON

OFF

OFF

OFF

ON

ON

NB!
Switch off the power supply before changing the hardware switches.

The address change will come into effect at the next power-up, and can be read in par. DN-02 MAC ID.

3.1.2 Setting the DeviceNet Address via par. DN-02 MAC ID

The address can be set via par. DN-02 MAC ID if the hardware switches are set to 63 (factory setting). The address change will come into effect at the next power-
up.

3.1.3 Setting the DeviceNet Address with the Object Class Code 0x03, Attribute 1, Instance 1

The address can be set via the DeviceNet object class code 0x03 attribute 1 command if the hardware switch is set to 63 (factory setting). A new address becomes
effective immediately after the class code 0x03, Instance 1, Attribute 1 command.

AF-600FP /650 GP DeviceNet Operating Instructions