DN-01 Baud Rate Select

Select the fieldbus transmission speed. The selection must correspond to the transmission speed of the master and the other network nodes.

Option:

Function:

[16]

10 Kbps

[17]

20 Kbps

[18]

50 Kbps

[19]

100 Kbps

[20] *

125 Kbps

[21]

250 Kbps

[22]

500 Kbps

DN-02 MAC ID

Range:

Function:

63. N/A*

[0 - 63. N/A]

Selection of station address. Every station connected to the same DeviceNet network must have an
unambiguous address.

DN-05 Readout Transmit Error Counter

Range:

Function:

0 N/A*

[0 - 255 N/A]

View the number of CAN control transmission errors since the last power-up.

DN-06 Readout Receive Error Counter

Range:

Function:

0 N/A*

[0 - 255 N/A]

View the number of CAN control receipt errors since the last power-up.

DN-07 Readout Bus Off Counter

Range:

Function:

0 N/A*

[0 - 255 N/A]

View the number of network Off events since the last power-up.

DN-10 Process Data Type Selection

Option:

Function:

Select the Instance (message) for data transmission. The Instances available are dependent upon the
setting of par. O-10 Control Word Profile.
When par. O-10 Control Word Profile is set to [0] Drive protocol, par. DN-10 Process Data Type Selection
options [0] and [1] are available.
When par. O-10 Control Word Profile is set to [5] ODVA, par. DN-10 Process Data Type Selection options
[2] and [3] are available.
Instances 100/150 and 101/151 are GE-specific. Instances 20/70 and 21/71 are ODVA-specific AC Drive
profiles.
For guidelines in message selection, please refer to the DeviceNet Operating Instructions.
Note that a change to this parameter will be executed immediately.

[0] *

INSTANCE 100/150

[1]

INSTANCE 101/151

[2]

INSTANCE 20/70

[3]

INSTANCE 21/71

DN-11 Process Data Config Write

Select the process write data for I/O Assembly Instances 101/151. Elements [2] and [3] of this array can be selected. Elements [0] and [1] of the array are fixed.

Option:

Function:

Select the process write data for I/O Assembly Instances 101/151. Elements [2] and [3] of this array can be selected. Elements [0] and [1] of the array are fixed.

AF-600FP /650 GP DeviceNet Operating Instructions