2 How to Install

2.1 Cabling

2.1.1 Cable Lengths

Baud rate

Max total cable length

Drop length

Maximum per drop

Cumulative maximum

125k baud

500 meters (1640 ft.)

6 meters (20 ft.) for one drop

156 meters (512 ft.)

250k baud

250 meters (820 ft.)

78 meters (256 ft.)

500k baud

100 meters (328 ft.)

39 meters (128 ft.)

2.1.2 Cable Specifications

The cable used should be according to ODVA specifications.

Be aware that the ODVA “Flat Cable” is an unscreened cable type, and is not
suited for use with frequency converters.

Illustration 2.1: ODVA “Thin Cable” cross section