2 how to install, 1 cabling – GE Industrial Solutions AF-650 GP DeviceNet User Manual
Page 8
Advertising
2 How to Install
2.1 Cabling
2.1.1 Cable Lengths
Baud rate
Max total cable length
Drop length
Maximum per drop
Cumulative maximum
125k baud
500 meters (1640 ft.)
6 meters (20 ft.) for one drop
156 meters (512 ft.)
250k baud
250 meters (820 ft.)
78 meters (256 ft.)
500k baud
100 meters (328 ft.)
39 meters (128 ft.)
2.1.2 Cable Specifications
The cable used should be according to ODVA specifications.
Be aware that the ODVA “Flat Cable” is an unscreened cable type, and is not
suited for use with frequency converters.
Illustration 2.1: ODVA “Thin Cable” cross section