GE Industrial Solutions AF-650 GP DeviceNet User Manual

Page 25

Advertising
background image

Bit 08, Speed reference/speed = reference:
Bit 08 = 0 means that the motor is running, but that the present speed is different from the preset speed reference. It might, for example, be the case while the
speed is being accelerated/decelerated during start/stop.
Bit 08 = 1 means that the present motor present speed matches the preset speed reference.

Bit 09, Local operation/bus control:
Bit 09 = 0 means that [STOP/RESET] is activated on the control unit, or that Local control in par. F-02 Operation Method is selected. It is not possible to control the
frequency converter via serial communication.
Bit 09 = 1 means that it is possible to control the frequency converter via the fieldbus/ serial communication.

Bit 10, Out of frequency limit:
Bit 10 = 0, if the output frequency has reached the value in par. H-72 Warning Speed Low or par. H-73 Warning Speed High.
Bit 10 = "1" means that the output frequency is within the defined limits.

Bit 11, No operation/in operation:
Bit 11 = 0 means that the motor is not running.
Bit 11 = 1 means that the frequency converter has a start signal or that the output frequency is greater than 0 Hz.

Bit 12, Drive OK/stopped, auto start:
Bit 12 = 0 means that there is no temporary over temperature on the drive.
Bit 12 = 1 means that the drive has stopped because of over temperature, but that the unit has not tripped and will resume operation once the over temperature
stops.

Bit 13, Voltage OK/limit exceeded:
Bit 13 = 0 means that there are no voltage warnings.
Bit 13 = 1 means that the DC voltage in the frequency converters intermediate circuit is too low or too high.

Bit 14, Torque OK/limit exceeded:
Bit 14 = 0 means that the motor current is lower than the torque limit selected in par. F-40 Torque Limiter (Driving) or par. F-41 Torque Limiter (Braking).
Bit 14 = 1 means that the torque limits in par. F-40 Torque Limiter (Driving) and par. F-41 Torque Limiter (Braking) have been exceeded.

Bit 15, Timer OK/limit exceeded:
Bit 15 = 0 means that the timers for motor thermal protection and drive thermal protection, respectively, have not exceeded 100%.
Bit 15 = 1 means that one of the timers has exceeded 100%.

AF-600FP /650 GP DeviceNet Operating Instructions

24