Par. o-10 control word profile (se, Par. o-10 control word profile, In par. o-50 coasting select – GE Industrial Solutions AF-650 GP DeviceNet User Manual

Page 39: Par. o-05 end-of-timeout function

Advertising
background image

defines whether to resume the set-up used before the time-out or to retain the set-up endorsed by the
time-out function.

[8]

Select setup 2

See [7] Select setup 1

[9]

Select setup 3

See [7] Select setup 1

[10]

Select setup 4

See [7] Select setup 1

NB!
The following configuration is required in order to change the set-up after a time-out:
Set par. K-10 Active Set-up to [9] Multi set-up and select the relevant link in par. K-12 This Set-up Linked to.

O-05 End-of-Timeout Function

Option:

Function:

Select the action after receiving a valid control word following a time-out. This parameter is active only
when par. O-04 Control Word Timeout Function is set to [Set-up 1-4].

[0]

Hold set-up

Retains the set-up selected in par. O-04 Control Word Timeout Function and displays a warning, until par.
O-06 Reset Control Word Timeout toggles. Then the frequency converter resumes its original set-up.

[1] *

Resume set-up

Resumes the set-up active prior to the time-out.

O-06 Reset Control Word Timeout

This parameter is active only when Hold set-up [0] has been selected in par. O-05 End-of-Timeout Function.

Option:

Function:

[0] *

Do not reset

Retains the set-up specified in par. O-04 Control Word Timeout Function, following a control word time-
out.

[1]

Do reset

Returns the frequency converter to the original set-up following a control word time-out. The frequency
converter performs the reset and then immediately reverts to the Do not reset [0] setting

O-07 Diagnosis Trigger

This parameter has no function for DeviceNet.

Option:

Function:

[0] *

Disable

[1]

Trigger on alarms

[2]

Trigger alarm/warn.

O-10 Control Word Profile

Instances 20/70 and 21/71 are selectable in par. DN-10 Process Data Type Selection.

Option:

Function:

[0] *

Drive Profile

[1]

PROFIdrive profile

[5]

ODVA

[7]

CANopen DSP 402

O-50 Coasting Select

Option:

Function:

Select control of the coasting function via the terminals (digital input) and/or via the network.

[0]

Digit Input

[1]

Bus

[2]

Logic AND

[3] *

Logic OR

AF-600FP /650 GP DeviceNet Operating Instructions

38