5.3.14 Class ID 28 Motor Data Object

In this object, the current motor data can be configured and read out. The Instances, attributes and services supported for this class are listed below.

5.3.15 Class ID 0/28 Motor Data Object

Attribute

Access

Name

Data type

Generic maxi-
mum values

Units

Default

Description

Parameter
reference

3

Get/set

Motor type

USINT

7

7

7 = Squirrel Cage Induction Motor

par. P-20 Motor Con-

struction

6

Get/set

Rated cur-
rent

UNIT

0-100.00

100mA

Drive dependent

Stator Current rating (from motor nameplate) par. P-03 Motor Current

7

Get/set

Rated volt-
age

UNIT

200-500

volt

Drive dependent

Base Voltage rating (from motor nameplate)

par. F-05 Motor Rated

Voltage

8

Get/set

Rated pow-
er

UDINT

0-18500

Watt

Drive dependent

Power rating at rated frequency (from motor
nameplate)

par. P-07 Motor Power

[kW]

9

Get/set

Rated fre-
quency

UNIT

1-1000

Hz

Drive dependent

Elec. frequency rating (from motor name-
plate)

par. F-04 Base Frequen-

cy

12

Get/set

Pole count

UINT

Drive dependent

Number of poles in the motor

par. P-01 Motor Poles

15

Get/set

Base speed UNIT

100-60000

RPM

Drive dependent

Nominal motor speed (from motor name-
plate)

par. P-06 Base Speed

* only on AF-650 GP drive

5.3.16 Class ID 29h Control Supervisory Object

The Control Supervisory Object can be used for process control and monitoring of the frequency converter, as an alternative to the I/O Instances defined in the
section “How to control the Frequency Converter”.

The attributes supported for this class are listed below.

5.3.17 Class ID 0x29

Attribute

Access

Name

Data type

Min/
Max

Default

Description

3

Get/Set

Run 1

Bool

0-1

Run Fwd, see note below

4

Get/Set

Run 2

Bool

0-1

Run rev, see note below

5

Get/Set

NetCtrl

Bool

0-1

1

0 = Local Control
1 = Control from Network

6

Get

State

USINT

0-7

0 = Vendor specific
1 = Start up
2 = Not ready
3 = Ready
4 = Enabled
5 = Stopping
6 = Fault stop
7 = Fault

7

Get

Running 1

Bool

0-1

0

0 = Other state
1 = (Enable and Run 1)
or (Stopping and Running 1)
or (Fault Stop and Running 1)

8

Get

Running 2

Bool

0-1

0

0 = Other state
1 = (Enable and Run 2)
or (Stopping and Running 2)
or (Fault Stop and Running 2)

9

Get

Ready

Bool

0-1

0 = Other state
1 = Ready or Enabled or Stopping

10

Get

Fault

Bool

0-1

0

0 = No Faults Present
1 = Fault Occured (latched)

12

Get/Set

Fault Rst

Bool

0-1

0 = No Action
1 ->1 = Reset Fault

13

Get

Fault Code

UINT

15

Get

Ctrl From Net

Bool

0-1

1

0 = Control is local
1 = Control is from Network

16

Get/Set

DN Fault Mode

UINT

0-2

1

Action on loss of DeviceNet
0 = Fault + Stop
1 = Ignore (Warning Optional)
2 = Drive specific

NB!
The ODVA drive profile selected in par. P-20 Motor Construction is available only when Instances 20/70 or 21/71 are selected.

AF-600FP /650 GP DeviceNet Operating Instructions