The State – Transition diagram below shows how the frequency converter will respond to the various command attributes associated with Class ID 0x29.

5.3.18 Class ID 2Ah AC/DC Drive Object

Use this object to set and read out a range of AF-600 FP or AF-650 GP drive control and status information. The attributes supported for this class are listed below.

5.3.19 Class ID 0x2A

Attribute

Access

Name

Data
type

Min/
Max

Default

Description

3

Get

At Reference

Bool

0-1

0 = Drive not at reference
1 = Drive at reference

4

Get/Set

Net REf

Bool

0-1

1

0 = Set reference at non-DeviceNet reference
1 = Set reference at DeviceNet reference

6

Get/Set

Drive Mode

USINT

0-1

1

0 = Vendor specific mode
1 = Open loop speed (Frequency)
2 = Closed loop speed control

7

Get

Speed Actual

INT

RPM/2

Speed Scale

Actual drive speed
(best approximation)

8

Get/Set

Speed Ref

INT

RPM/2

Speed Scale

Speed reference

22

Get/Set

Speed Scale

SINT

-128-127

Speed scaling factor

29

Get

Ref from Net

Bool

0-1

0 = Local speed reference
1 = DeviceNet speed reference

5.3.20 Class ID 2Bh (Acknowledge Handler Object)

Use this object to manage message reception acknowledgements, necessary for Change-Of-State support.

The attributes supported for this class are listed below.

5.3.21 Class ID 0x2B

Attribute

Access

Name

Data
type

Min/
Max

Default

Description

1

Set

ACK Timer

UINT

0-65535

16

Time top wait for ACK before resending

2

Get/Set

Retry Timer

USINT

0-255

1

Number of ACK-timeouts to wait before producing.
RetryLimit_Reache event.

3

Get/Set

COS

UINT

Connection instance ID

AF-600FP /650 GP DeviceNet Operating Instructions