Example:
par. P-06 Base Speed = 1420 RPM
par. F-04 Base Frequency = 50 Hz
par. F-53 Maximum Reference = 1420 RPM

In order to run the motor at 25%, the reference transmitted must be: (1420*0,25) = 355 = 163hex

163hex => 25% => Fout = 12,5Hz

4.4.4 Actual Output Speed under Instances 20/70 and 21/71

The value of the actual speed of the motor is transmitted in the form of a 16-bit word. The value is transmitted as a whole number. Negative figures are formed
by means of 2s complement.

The actual speed value has the following format:

-32767 (8000 Hex) [RPM] -> +32767 [RPM] (7FFF Hex) [RPM]

4.5 GE Drive Control Profile

4.5.1 Control Word under Instances 100/150, 101/151 and 102/152

To select GE drive protocol in the control word, par. O-10 Control Word Pro-
file
must be set to Drive protocol [0]. The control word is used to send
commands from a master (PLC or PC) to a slave (frequency converter).

The control words in Instances 100/101/102 are defined as follows to the
right:

Bit

Bit value = 0

Bit value = 1

00

Reference value

External selection lsb

01

Reference value

External selection msb

02

DC brake

Ramp

03

Coasting

No coasting

04

Quick stop

Ramp

05

Hold output frequency

Use ramp

06

Ramp stop

Start

07

No function

Reset

08

No function

Jog

09

Ramp 1

Ramp 2

10

Data invalid

Data valid

11

No function

Relay 01 active

12

No function

Relay 04 active

13

Parameter set-up

Selection lsb

14

Parameter set-up

Selection msb

15

No function

Reverse

Explanation of the Control Bits:

Bits 00/01
Bits 00 and 01 are used to choose between the four reference values, which are pre-programmed in par. C-05 Multi-step Frequency 1 - 8 according to the table
to the right: