7 Application Examples

7.1 Example: Working with Instance 101/151 Process

This example shows how to work with I/O Instance 101/151, which consists
of Control Word/Status Word and Reference/Main Actual Value. The Instance
101/151 also has two additional words, which can be programmed to monitor
process signals, as shown in the figure.

The application requires monitoring of the motor torque and digital input, so
PCD 3 is set up to read the actual motor torque. PCD 4 is set up to monitor
the state of an external sensor via the process signal digital input. The sensor
is connected to digital input 18.

An external device is also controlled via control word bit 11 and the built-in
relay of the frequency converter.

Reversing is permitted only when the reversing bit 15 in the control word and
the digital input 19 are set to high.

For safety reasons the frequency converter will stop the motor if the Device-
Net cable is broken, the master has a system failure, or the PLC is in stop
mode.

Parameter

Function

Setting

par. H-08 Reverse Lock

Motor speed range/direction

Both directions [2]

par. E-01 Terminal 18 Digital Input

Digital input 18

No operation [0]

par. E-02 Terminal 19 Digital Input

Digital input 19

Reversing [10]

par. E-24 Function Relay

Function relay

Control word bit 11 [36]
Control word bit 12 [37]

par. O-03 Control Word Timeout Time

Control word timeout time

1.0 sec

par. O-04 Control Word Timeout Function

Control word timeout function

Stop [2]

par. O-10 Control Word Profile

Control word profile

Drive Profile

par. O-50 Coasting Select

Coasting select

Bus [1]

par. O-51 Quick Stop Select

Quick-stop select

Bus [1]

par. O-52 DC Brake Select

DC-brake select

Bus [1]

par. O-53 Start Select

Start select

Bus [1]

par. O-54 Reversing Select

Reversing select

Logic AND [2]

par. O-55 Set-up Select

Set-up select

Bus [1]

par. O-56 Preset Reference Select

Preset reference select

Bus [1]

par. DN-01 Baud Rate Select

Baud rate select

- set to match other DeviceNet stations

par. DN-02 MAC ID

MAC ID

- set desired station address

par. DN-10 Process Data Type Selection

Process data type selection

Instance 101/151 [1]

par. DN-12 Process Data Config Read

Process Data Config Read

PCD 3: Torque
PCD 4: Digital input

AF-600FP /650 GP DeviceNet Operating Instructions

47