Advertising
background image

3.1.4 Baud Rate Setting

All DeviceNet stations connected to the same bus network must have the same Baud rate. The baud rate of the frequency converter can be selected via:

-

Hardware switches

-

par. DN-01 Baud Rate Select (default 125k Baud)

-

Object Class code 0x03, Instance 1, Attribute 2.

3.1.5 Setting the DeviceNet Baud Rate using the Hardware Switches

Using the hardware switches it is possible to select a baud rate of 125k baud
(factory setting), 250k baud or 500 k baud according to the following table:

Baud rate switch

8

7

par. DN-01 Baud Rate Select

1

1

125 k Baud

0

0

250 k Baud

0

1

500 k Baud

1

0

NB!
Switch off the power supply before changing the hardware switches.

The baud rate change will come into effect at the next power-up, and can be read in par. DN-01 Baud Rate Select.

3.1.6 Setting the DeviceNet Baud Rate via par. DN-01 Baud Rate Select

The baud rate can be set via par. DN-01 Baud Rate Select if the hardware switches 1 and 2 are set to ON (factory setting). The baud rate change will come into
effect at the next power-up.

3.1.7 Setting the DeviceNet Baud Rate with the Object Class Code 0x03 Attribute 2

The baud rate can be set via the DeviceNet object class code 0x03 attribute 2 command, if the hardware switches 1 and 2 are set to ON (factory setting). A new
baud rate becomes effective immediately after the class code 0x03 attribute 2 command.

AF-600FP /650 GP DeviceNet Operating Instructions