To par. o-56 preset ref- erence select – GE Industrial Solutions AF-650 GP DeviceNet User Manual

Page 41

Advertising
background image

NB!
This parameter is only active when par. O-01 Control Site is set to [0] Digital and control word.

O-55 Set-up Select

Option:

Function:

Select control of the frequency converter set-up selection via the terminals (digital input) and/or via the
network.

[0]

Digit Input

Activates the set-up selection via a digital input.

[1]

Bus

Activates the set-up selection via the serial communication port or network option module.

[2]

Logic AND

Activates the set-up selection via the network/serial communication port, AND additionally via one of the
digital inputs.

[3] *

Logic OR

Activate the set-up selection via the network/serial communication port OR via one of the digital inputs.

NB!
This parameter is active only when par. O-01 Control Site is set to [0] Digital and control word.

O-56 Preset Reference Select

Option:

Function:

Select control of the frequency converter Preset Reference selection via the terminals (digital input) and/
or via the network.

[0]

Digit Input

Activates Preset Reference selection via a digital input.

[1]

Bus

Activates Preset Reference selection via the serial communication port or network option module.

[2]

Logic AND

Activates Preset Reference selection via the network/serial communication port, AND additionally via one
of the digital inputs.

[3] *

Logic OR

Activates the Preset Reference selection via the network/serial communication port OR via one of the
digital inputs.

NB!
This parameter is active only when par. O-01 Control Site is set to [0] Digital and control word.

O-90 Bus Jog 1 Speed

Range:

Function:

100 RPM*

[0 - par. H-13 RPM]

Enter the jog speed. This is a fixed jog speed activated via the serial port or network option.

O-91 Bus Jog 2 Speed

Range:

Function:

200 RPM*

[0 - par. H-13 RPM]

Enter the jog speed. This is a fixed jog speed activated via the serial port or network option.

DN-00 DeviceNet Protocol

Option:

Function:

[0]

CANopen

[1] *

DeviceNet

View the active CAN protocol.

NB!
The options depend on installed option.

AF-600FP /650 GP DeviceNet Operating Instructions

40

6

Advertising