background image

4.4 ODVA Control Profile

4.4.1 Control Word under Instances 20/70 and 21/71

Control Word under Instances 20/70 and 21/71 Set par. O-10 Control Word
Profile
to
ODVA, and select the instance in par. DN-10 Process Data Type Se-
lection
.

The control word in Instances 20 and 21 is defined in the overview to the right:

NB!
Note that the bits 00 and 02 in Instance 20 are identical with bits 00 and 02
in the more extensive Instance 21.

Bit

Instance 20

Instance 21

Bit = 0

Bit = 1

Bit = 0

Bit = 1

00

Stop

Run Fwd

Stop

Run Fwd

01

-

-

Stop

Run Rev

02

No function Fault reset

No function Fault reset

03

-

-

-

-

04

-

-

-

-

05

-

-

-

Net Ctrl

06

-

-

-

Net Ref

07-15

-

-

-

-

Explanation of the Bits:

Bit 0, Run Fwd:
Bit 0 = "0" means that the frequency converter has a stop command.
Bit 0 = "1" leads to a start command and the frequency converter will start to run the motor clockwise.

Bit 1, Run Rev:
Bit 1 = "0" leads to a stop of the motor.
Bit 1 = "1" leads to a start of the motor.

Bit 2, Fault Reset:
Bit 2 = "0" means that there is no reset of a trip.
Bit 2 = "1" means that a trip is reset.

Bit 3, No function:
Bit 3 has no function.

Bit 4, No function:
Bit 4 has no function.

AF-600FP /650 GP DeviceNet Operating Instructions

17

4