The effect of control mode upon the function of par. O-53 Start Select and par. O-54 Reversing Select:

If Digital Input [0] is selected, the terminals will control the start and reversing
functions

Par. O-53/54 setting: Digital input [0]
Terminal

Bit 06/15

Function

0

0

Stop/Anti-clockwise

0

1

Stop/Anti-clockwise

1

0

Start/Clockwise

1

1

Start/Clockwise

If Bus [1] is selected, commands will be activated only when given via the
control word.

Par. O-53/54 setting: Bus [1]
Terminal

Bit 02/03/04

Function

0

0

Stop/Anti-clockwise

0

1

Start/Clockwise

1

0

Stop/Anti-clockwise

1

1

Start/Clockwise

If Logic AND [2] is selected, both signals must be activated to perform the
function.

Par. O-53/54 setting: Logic AND [2]
Terminal

Bit 02/03/04

Function

0

0

Stop/Anti-clockwise

0

1

Stop/Anti-clockwise

1

0

Stop/Anti-clockwise

1

1

Start/Clockwise

If Logic OR [3] is selected, activation of one signal will activate the function.

Par. O-53/54 setting: Logic OR [3]
Terminal

Bit 02/03/04

Function

0

0

Stop/Anti-clockwise

0

1

Start/Clockwise

1

0

Start/Clockwise

1

1

Start/Clockwise

The effect of control mode upon the function of par. O-55 Set-up Select and par. O-56 Preset Reference Select:

If Digital input [0] is selected, the terminals will control the set-up and preset
reference functions.

Par. O-55/56 setting: Digital input [0]
Terminal

Bit 00/01, 13/14

Function

Msb

Lsb

Msb

Lsb

Preset ref., Set-up no.

0

0

0

0

1

0

0

0

1

1

0

0

1

0

1

0

0

1

1

1

0

1

0

0

2

0

1

0

1

2

0

1

1

0

2

0

1

1

1

2

1

0

0

0

3

1

0

0

1

3

1

0

1

0

3

1

0

1

1

3

1

1

0

0

4

1

1

0

1

4

1

1

1

0

4

1

1

1

1

4

AF-600FP /650 GP DeviceNet Operating Instructions

52

8

Advertising