3.2 Mechanical Installation

3.2.1 Mechanical mounting

All IP20 .

If the P21/Nema 1 field installed option kits are installed, there must be a clearance of a minimum of 50mm or 2 inches between drives.

For optimal cooling conditions allow a free air passage above and below the frequency converter. See table below.

Air passage for different Unit Sizes

Unit

Size:

12

13

15

21

22

23

24

31

32

33

34

a (mm):

100

100

100

200

200

200

200

200

225

200

225

b (mm):

100

100

100

200

200

200

200

200

225

200

225

Table 3.1:

1.

Drill holes in accordance with the measurements given.

2.

You must provide screws suitable for the surface on which you want to mount the frequency converter. Retighten all four screws.

Table 3.2: Mounting Unit Sizes 15, 21, 22, 23, 24, 31, 32, 33 and 34 on a non-solid back wall, the drive must be provided with a back plate A due to insufficient
cooling air over the heat sink.

AF-650 GP Operating Instructions