4.2 Quick Setup Parameter List

K-01 Language

Option:

Function:

Defines the language to be used in the display.

The frequency converter is delivered with 4 different languages.

[0] *

English

Part of Language packages 1 - 4

K-02 Motor Speed Unit

Option:

Function:

This parameter cannot be adjusted while the motor is running.
The display showing depends on settings in par. K-02 Motor Speed Unit and par. K-03 Regional Settings.
The default setting of par. K-02 Motor Speed Unit and par. K-03 Regional Settings depends on which region
of the world the frequency converter is supplied to, but can be re-programmed as required.

NB!
Changing the Motor Speed Unit will reset certain parameters to their initial value. It is recommended to
select the motor speed unit first, before modifying other parameters.

[0]

RPM

Selects display of motor speed variables and parameters (i.e. references, feedbacks and limits) in terms
of motor speed (RPM).

[1] *

Hz

Selects display of motor speed variables and parameters (i.e. references, feedbacks and limits) in terms
of output frequency to the motor (Hz).

P-02 Motor Power [HP]

Range:

Function:

4.00 hp*

[0.09 - 3000.00 hp]

Enter the nominal motor power in HP according to the motor nameplate data. The default value corre-
sponds to the nominal rated output of the unit. This parameter is visible in Keypad if par. K-03 Region-
al Settings is US [1]

P-07 Motor Power [kW]

Range:

Function:

4.00 kW*

[0.09 - 3000.00 kW]

Enter the nominal motor power in kW according to the motor nameplate data. The default value corre-
sponds to the nominal rated output of the unit.
This parameter cannot be adjusted while the motor is running. This parameter is visible in Keypad if par.
K-03 Regional Settings is International [0].

F-05 Motor Rated Voltage

Range:

Function:

400. V*

[10. - 1000. V]

Enter the nominal motor voltage according to the motor nameplate data. The default value corresponds
to the nominal rated output of the unit.
This parameter cannot be adjusted while the motor is running.

F-04 Base Frequency

Range:

Function:

50. Hz*

[20 - 1000 Hz]

Min - Max motor frequency: 20 - 1000 Hz.
Select the motor frequency value from the motor nameplate data. If a value different from 50 Hz or 60
Hz is selected, it is necessary to adapt the load independent settings in par. H-50 Motor Magnetisation at
Zero Speed
to par. H-53 Model Shift Frequency. For 87 Hz operation with 230/400 V motors, set the name-
plate data for 230 V/50 Hz. Adapt par. F-17 Motor Speed High Limit [RPM] and par. F-53 Maxi-
mum Reference to the 87 Hz application.

AF-650 GP Operating Instructions

39