Illustration 3.13: Motor connection for unit sizes 31 and 32 Nema 12 or Nema
4 drive types (230V, 20 to 50HP, 460V, 40 to 100HP, 575V, 40 to 125HP)

Illustration 3.14: Motor connection for unit sizes 33 and 34 IP20 Open Chas-
sis drive types (230V, 25 to 50HP, 460V, 50 to 100HP, 575V, 50 to 125HP).

Illustration 3.15: Cable entry holes for unit size 21. The suggested use of the
holes are purely recommendations and other solutions are possible.

Illustration 3.16: Cable entry holes for unit size 22. The suggested use of the
holes are purely recommendations and other solutions are possible.

Illustration 3.17: Cable entry holes for unit size 31. The suggested use of the
holes are purely recommendations and other solutions are possible.

Illustration 3.18: Cable entry holes for unit size 32. The suggested use of the
holes are purely recommendations and other solutions are possible.

Term. no.

96

97

98

99

U

V

W

PE

1)

Motor voltage 0-100% of mains voltage.
3 wires out of motor

U1

V1

W1

PE

1)

Delta-connected

W2

U2

V2

6 wires out of motor

U1

V1

W1

PE

1)

Star-connected U2, V2, W2
U2, V2 and W2 to be interconnected separately.

1)

Protected Earth Connection