5.3 Electrical Data - 525-600 V

Mains Supply 3 x 525 - 600 VAC (AF-650 GP only)
AF-650 GP

Typical Shaft Output [kW]

0.75

1.1

1.5

2.2

3

4

5.5

7.5

Typical Shaft Output [HP] at 575V

1.0

1.5

2.0

2.9

4.0

5.0

7.5

10

Unit Size IP20, 21

12

12

12

12

12

12

13

13

Unit Size IP55

15

15

15

15

15

15

15

15

Output current

Continuous
(3 x 525-550 V ) [A]

1.8

2.6

2.9

4.1

5.2

6.4

9.5

11.5

Intermittent
(3 x 525-550 V ) [A]

2.9

4.2

4.6

6.6

8.3

10.2

15.2

18.4

Continuous
(3 x 551-600 V ) [A]

1.7

2.4

2.7

3.9

4.9

6.1

9.0

11.0

Intermittent
(3 x 551-600 V ) [A]

2.7

3.8

4.3

6.2

7.8

9.8

14.4

17.6

Continuous kVA (525 V AC) [kVA]

1.7

2.5

2.8

3.9

5.0

6.1

9.0

11.0

Continuous kVA (575 V AC) [kVA]

1.7

2.4

2.7

3.9

4.9

6.1

9.0

11.0

Max. cable size
(mains, motor, brake)
[AWG]

2)

[mm

2

]

24 - 10 AWG

0.2 - 4 mm

2

24 - 10 AWG

0.2 - 4 mm

2

Max. input current

Continuous
(3 x 525-600 V ) [A]

1.7

2.4

2.7

4.1

5.2

5.8

8.6

10.4

Intermittent
(3 x 525-600 V ) [A]

2.7

3.8

4.3

6.6

8.3

9.3

13.8

16.6

Max. pre-fuses

1)

[A]

10

10

10

20

20

20

32

32

Environment
Estimated power loss
at rated max. load [W]

4)

35

50

65

92

122

145

195

261

Weight,
Unit Size IP20 [kg]

6.5

6.5

6.5

6.5

6.5

6.5

6.6

6.6

Weight,
Unit Size IP55 [kg]

13.5

13.5

13.5

13.5

13.5

13.5

14.2

14.2

Efficiency

4)

0.97

0.97

0.97

0.97

0.97

0.97

0.97

0.97