Mains Supply 3 x 525 - 600 VAC
AF-650 GP
High/ Normal Load*

HO

NO

HO

NO

HO

NO

HO

NO

HO

NO

Typical Shaft Output [kW]

11

15

15

18.5

18.5

22

22

30

30

37

Typical Shaft Output [HP] at
575V

15

20

20

25

25

30

30

40

40

50

Unit Size IP 21, 55, 66

21

21

22

22

31

Unit Size IP20

23

23

24

24

24

Output current

Continuous
(3 x 525-550 V ) [A]

19

23

23

28

28

36

36

43

43

54

Intermittent
(3 x 525-550 V ) [A]

30

25

37

31

45

40

58

47

65

59

Continuous
(3 x 525-600 V ) [A]

18

22

22

27

27

34

34

41

41

52

Intermittent
(3 x 525-600 V ) [A]

29

24

35

30

43

37

54

45

62

57

Continuous kVA (550 V AC)
[kVA]

18.1

21.9

21.9

26.7

26.7

34.3

34.3

41.0

41.0

51.4

Continuous kVA (575 V AC)
[kVA]

17.9

21.9

21.9

26.9

26.9

33.9

33.9

40.8

40.8

51.8

Max. cable size IP20
(mains, motor, load share and
brake)
[AWG]

2)

[mm

2

]

16(6)

35(2)

Max. cable size IP21, 55, 66
(mains, motor, load share and
brake)
[AWG]

2)

[mm

2

]

16(6)

35(2)

90 (3/0)

Max. input current

Continuous
at 550 V [A]

17.2

20.9

20.9

25.4

25.4

32.7

32.7

39

39

49

Intermittent
at 550 V [A]

28

23

33

28

41

36

52

43

59

54

Continuous
at 575 V [A]

16

20

20

24

24

31

31

37

37

47

Intermittent
at 575 V [A]

26

22

32

27

39

34

50

41

56

52

Max. pre-fuses

1)

[A]

63

63

63

80

100

Environment
Estimated power loss
at rated max. load [W]

4)

225

285

329

700

700

Weight,
Unit Size IP21, 55 [kg]

23

23

27

27

27

Weight,
Unit Size IP20 [kg]

12

12

23.5

23.5

23.5

Efficiency

4)

0.98

0.98

0.98

0.98