Af-650 gp operating instructions – GE Industrial Solutions AF-650 GP General Purpose Drive (230V to 50HP, 460_575V to 100HP) User Manual
Page 76
Mains Supply 3 x 525 - 600 VAC
AF-650 GP
High/ Normal Load*
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Typical Shaft Output [kW]
11
15
15
18.5
18.5
22
22
30
30
37
Typical Shaft Output [HP] at
575V
15
20
20
25
25
30
30
40
40
50
Unit Size IP 21, 55, 66
21
21
22
22
31
Unit Size IP20
23
23
24
24
24
Output current
Continuous
(3 x 525-550 V ) [A]
19
23
23
28
28
36
36
43
43
54
Intermittent
(3 x 525-550 V ) [A]
30
25
37
31
45
40
58
47
65
59
Continuous
(3 x 525-600 V ) [A]
18
22
22
27
27
34
34
41
41
52
Intermittent
(3 x 525-600 V ) [A]
29
24
35
30
43
37
54
45
62
57
Continuous kVA (550 V AC)
[kVA]
18.1
21.9
21.9
26.7
26.7
34.3
34.3
41.0
41.0
51.4
Continuous kVA (575 V AC)
[kVA]
17.9
21.9
21.9
26.9
26.9
33.9
33.9
40.8
40.8
51.8
Max. cable size IP20
(mains, motor, load share and
brake)
[AWG]
2)
[mm
2
]
16(6)
35(2)
Max. cable size IP21, 55, 66
(mains, motor, load share and
brake)
[AWG]
2)
[mm
2
]
16(6)
35(2)
90 (3/0)
Max. input current
Continuous
at 550 V [A]
17.2
20.9
20.9
25.4
25.4
32.7
32.7
39
39
49
Intermittent
at 550 V [A]
28
23
33
28
41
36
52
43
59
54
Continuous
at 575 V [A]
16
20
20
24
24
31
31
37
37
47
Intermittent
at 575 V [A]
26
22
32
27
39
34
50
41
56
52
Max. pre-fuses
1)
[A]
63
63
63
80
100
Environment
Estimated power loss
at rated max. load [W]
4)
225
285
329
700
700
Weight,
Unit Size IP21, 55 [kg]
23
23
27
27
27
Weight,
Unit Size IP20 [kg]
12
12
23.5
23.5
23.5
Efficiency
4)
0.98
0.98
0.98
0.98
0.98
AF-650 GP Operating Instructions
75
5