Af-650 gp operating instructions – GE Industrial Solutions AF-650 GP General Purpose Drive (230V to 50HP, 460_575V to 100HP) User Manual
Page 72
5.2 Electrical Data - 380-500 V
Mains Supply 3 x 380 - 500 VAC (AF-650 GP), 3 x 380 - 480 VAC (AF-650 GP)
AF-650 GP/AF-650 GP
Typical Shaft Output [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
Typical Shaft Output [HP] at 460V
0.5
0.7
1.0
1.5
2.0
2.9
4.0
5.0
7.5
10
Unit Size IP20/IP21
12
12
12
12
12
12
12
12
13
13
Unit Size IP20 (AF-650
GP only)
11
11
11
11
11
Unit Size IP55, 66
15
15
15
15
15
15
15
15
15
15
Output current
High overload 160% for 1 minute
Shaft output [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
Continuous
(3 x 380-440 V) [A]
1.3
1.8
2.4
3
4.1
5.6
7.2
10
13
16
Intermittent
(3 x 380-440 V) [A]
2.1
2.9
3.8
4.8
6.6
9.0
11.5
16
20.8
25.6
Continuous
(3 x 441-500 V) [A]
1.2
1.6
2.1
2.7
3.4
4.8
6.3
8.2
11
14.5
Intermittent
(3 x 441-500 V) [A]
1.9
2.6
3.4
4.3
5.4
7.7
10.1
13.1
17.6
23.2
Continuous KVA
(400 V AC) [KVA]
0.9
1.3
1.7
2.1
2.8
3.9
5.0
6.9
9.0
11.0
Continuous KVA
(460 V AC) [KVA]
0.9
1.3
1.7
2.4
2.7
3.8
5.0
6.5
8.8
11.6
Max. cable size
(mains, motor, brake)
[AWG]
2)
[mm
2
]
24 - 10 AWG
0.2 - 4 mm
2
24 - 10 AWG
0.2 - 4 mm
2
Max. input current
Continuous
(3 x 380-440 V ) [A]
1.2
1.6
2.2
2.7
3.7
5.0
6.5
9.0
11.7
14.4
Intermittent
(3 x 380-440 V ) [A]
1.9
2.6
3.5
4.3
5.9
8.0
10.4
14.4
18.7
23.0
Continuous
(3 x 441-500 V) [A]
1.0
1.4
1.9
2.7
3.1
4.3
5.7
7.4
9.9
13.0
Intermittent
(3 x 441-500 V) [A]
1.6
2.2
3.0
4.3
5.0
6.9
9.1
11.8
15.8
20.8
Max. pre-fuses
1)
[A]
10
10
10
10
10
20
20
20
32
32
Environment
Estimated power loss
at rated max. load [W]
4)
35
42
46
58
62
88
116
124
187
255
Weight,
Unit Size IP20
4.7
4.7
4.8
4.8
4.9
4.9
4.9
4.9
6.6
6.6
Unit Size IP55, 66
13.5
13.5
13.5
13.5
13.5
13.5
13.5
13.5
14.2
14.2
Efficiency
4)
0.93
0.95
0.96
0.96
0.97
0.97
0.97
0.97
0.97
0.97
0.37 - 7.5 kW only available as 160% high overload.
AF-650 GP Operating Instructions