Safe stop Terminal 37

2)

(Terminal 37 is fixed PNP logic):

Voltage level

0 - 24 V DC

Voltage level, logic'0' PNP

< 4 V DC

Voltage level, logic'1' PNP

>20 V DC

Nominal input current at 24 V

50 mA rms

Nominal input current at 20 V

60 mA rms

Input capacitance

400 nF

All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminals 27 and 29 can also be programmed as output.

2) Terminal 37 is only available in AF-650 GP. It can only be used as safe stop input. Terminal 37 is suitable for category 3 installations according to EN 954-1 (safe
stop according to category 0 EN 60204-1) as required by the EU Machinery Directive 98/37/EC. Terminal 37 and the Safe Stop function are designed in conformance
with EN 60204-1, EN 50178, EN 61800-2, EN 61800-3, and EN 954-1. For correct and safe use of the Safe Stop function follow the related information and instructions
in the AF-650 GP Design Guide.

Analog inputs:

Number of analog inputs

2

Terminal number

53, 54

Modes

Voltage or current

Mode select

Switch S201 and switch S202

Voltage mode

Switch S201/switch S202 = OFF (U)

Voltage level

-10 to +10 V (scaleable)

Input resistance, R

i

approx. 10 kΩ

Max. voltage

± 20 V

Current mode

Switch S201/switch S202 = ON (I)

Current level

0/4 to 20 mA (scaleable)

Input resistance, R

i

approx. 200 Ω

Max. current

30 mA

Resolution for analog inputs

10 bit (+ sign)

Accuracy of analog inputs

Max. error 0.5% of full scale

Bandwidth

100 Hz

The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.