Af-650 gp operating instructions – GE Industrial Solutions AF-650 GP General Purpose Drive (230V to 50HP, 460_575V to 100HP) User Manual

Page 82

Advertising
background image

Control card performance:

Scan interval

AF-650 GP: 1 ms

Control characteristics:

Resolution of output frequency at 0 - 1000 Hz

+/- 0.003 Hz

Repeat accuracy of Precise start/stop (terminals 18, 19)

≤± 0.1 msec

System response time (terminals 18, 19, 27, 29, 32, 33)

≤ 2 ms

Speed control range (open loop)

1:100 of synchronous speed

Speed control range (closed loop)

1:1000 of synchronous speed

Speed accuracy (open loop)

30 - 4000 rpm: error ±8 rpm

Speed accuracy (closed loop), depending on resolution of feedback device

0 - 6000 rpm: error ±0.15 rpm

All control characteristics are based on a 4-pole asynchronous motor

Surroundings:

Enclosure

IP20 Open Chassis, Nema 1 with field installed kit, Nema 12, and Nema 4

Vibration test

1.0 g

Max. relative humidity

5% - 93%(IEC 721-3-3; Class 3K3 (non-condensing) during operation

Aggressive environment (IEC 60068-2-43) H

2

S test

class Kd

Ambient temperature

Max. 50 °C

1) Only for

3.7 kW (200 - 240 V), 7.5 kW (400 - 480/ 500 V)

2) As enclosure kit for

3.7 kW (200 - 240 V), 7.5 kW (400 - 480/ 500 V)

3) Derating for high ambient temperature, see special conditions in the Design Guide

Minimum ambient temperature during full-scale operation

0 °C

Minimum ambient temperature at reduced performance

- 10 °C

Temperature during storage/transport

-25 - +65/70 °C

Maximum altitude above sea level without derating

1000 m

Derating for high altitude, see special conditions in the Design Guide

EMC standards, Emission

EN 61800-3, EN 61000-6-3/4, EN 55011

EMC standards, Immunity

EN 61800-3, EN 61000-6-1/2,

EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6

See section on special conditions in the Design Guide. Please see www.geelectrical.com/drives for more information.

Protection and Features:

Electronic thermal motor protection against overload.

Temperature monitoring of the heatsink ensures that the frequency converter trips if the temperature reaches a predefined level. An overload temper-
ature cannot be reset until the temperature of the heatsink is below the values stated in the tables on the following pages (Guideline - these temperatures
may vary for different power sizes, Unit Sizes, enclosure ratings etc.).

The frequency converter is protected against short-circuits on motor terminals U, V, W.

If a mains phase is missing, the frequency converter trips or issues a warning (depending on the load).

Monitoring of the intermediate circuit voltage ensures that the frequency converter trips if the intermediate circuit voltage is too low or too high.

The frequency converter constantly checks for critical levels of internal temperature, load current, high voltage on the intermediate circuit and low motor
speeds. As a response to a critical level, the frequency converter can adjust the switching frequency and/ or change the switching pattern in order to
ensure the performance of the drive.