Af-650 gp operating instructions – GE Industrial Solutions AF-650 GP General Purpose Drive (230V to 50HP, 460_575V to 100HP) User Manual

Page 81

Advertising
background image

Control card, RS 485 serial communication:

Terminal number

68 (P,TX+, RX+), 69 (N,TX-, RX-)

Terminal number 61

Common for terminals 68 and 69

The RS 485 serial communication circuit is functionally separated from other central circuits and galvanically isolated from the supply voltage (PELV).

Control card, USB serial communication:

USB standard

1.1 (Full speed)

USB plug

USB type B “device” plug

Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
The USB ground connection is not galvanically isolated from protection earth. Use only an isolated laptop as PC connection to the USB connector on the frequency
converter.

Relay outputs:

Programmable relay outputs

2 Form C

Relay 01 Terminal number

1-3 (break), 1-2 (make)

Max. terminal load (AC-1)

1)

on 1-3 (NC), 1-2 (NO) (Resistive load)

240 V AC, 2 A

Max. terminal load (AC-15)

1)

(Inductive load @ cosφ 0.4)

240 V AC, 0.2 A

Max. terminal load (DC-1)

1)

on 1-2 (NO), 1-3 (NC) (Resistive load)

60 V DC, 1A

Max. terminal load (DC-13)

1)

(Inductive load)

24 V DC, 0.1A

Relay 02 Terminal number

4-6 (break), 4-5 (make)

Max. terminal load (AC-1)

1)

on 4-5 (NO) (Resistive load)

2)3)

Overvoltage cat. II

400 V AC, 2 A

Max. terminal load (AC-15)

1)

on 4-5 (NO) (Inductive load @ cosφ 0.4)

240 V AC, 0.2 A

Max. terminal load (DC-1)

1)

on 4-5 (NO) (Resistive load)

80 V DC, 2 A

Max. terminal load (DC-13)

1)

on 4-5 (NO) (Inductive load)

24 V DC, 0.1A

Max. terminal load (AC-1)

1)

on 4-6 (NC) (Resistive load)

240 V AC, 2 A

Max. terminal load (AC-15)

1)

on 4-6 (NC) (Inductive load @ cosφ 0.4)

240 V AC, 0.2A

Max. terminal load (DC-1)

1)

on 4-6 (NC) (Resistive load)

50 V DC, 2 A

Max. terminal load (DC-13)

1)

on 4-6 (NC) (Inductive load)

24 V DC, 0.1 A

Min. terminal load on 1-3 (NC), 1-2 (NO), 4-6 (NC), 4-5 (NO)

24 V DC 10 mA, 24 V AC 20 mA

Environment according to EN 60664-1

overvoltage category III/pollution degree 2

1) IEC 60947 part 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
2) Overvoltage Category II
3) UL applications 300 V AC 2A

Cable lengths and cross sections for control cables*:

Max. motor cable length, screened

150 m

Max. motor cable length, unscreened

300 m

Maximum cross section to control terminals, flexible/ rigid wire without cable end sleeves

1.5 mm

2

/16 AWG

Maximum cross section to control terminals, flexible wire with cable end sleeves

1 mm

2

/18 AWG

Maximum cross section to control terminals, flexible wire with cable end sleeves with collar

0.5 mm

2

/20 AWG

Minimum cross section to control terminals

0.25 mm

2

/ 24 AWG

* Power cables, see tables in section “Electrical Data” of the AF-650 GP Design Guide

AF-650 GP Operating Instructions

80

5