4.1.2 Initial Commissioning

The easiest way of carrying out the initial commissioning is by using the Quick Menu button and follow the quick set-up procedure using Keypad (read table from
left to right). The example applies to open loop applications:

Press

Q2 Quick Set-Up

par. K-01 Language

Set language

par. K-02 Motor Speed Unit

Set motor speed in Hz or RPM

par. P-02 Motor Power [HP] or par. P-07 Motor
Power [kW]

Set Motor nameplate power

par. F-05 Motor Rated Voltage

Set Nameplate voltage

par. F-04 Base Frequency

Set Nameplate frequency

par. P-03 Motor Current

Set Nameplate current

par. P-06 Base Speed

Set Nameplate speed in RPM

par. F-01 Frequency Setting 1

Set reference source

par. F-02 Operation Method

Select which reference site to activate

par. F-07 Accel Time 1

Set the accel time with reference to synchronous motor speed, n

s

par. F-08 Decel Time 1

Set the decel time time with reference to synchronous motor speed,
n

s

par. F-10 Electronic Overload

Set motor thermal protection

par. F-15 Motor Speed High Limit [Hz] or par.
F-17 Motor Speed High Limit [RPM]

Set motor speed high limit in Hz or RPM

par. F-16 Motor Speed Low Limit [Hz] or par.
F-18 Motor Speed Low Limit [RPM]

Set motor speed low limit in Hz or RPM

par. H-08 Reverse Lock

Set allowed rotation direction

par. P-04 Auto Tune

Set desired auto tune function. Enable complete auto tune is rec-
ommended

AF-650 GP Operating Instructions

38