Af-650 gp operating instructions – GE Industrial Solutions AF-650 GP General Purpose Drive (230V to 50HP, 460_575V to 100HP) User Manual
Page 74
Mains Supply 3 x 380 - 500 VAC (AF-650 GP), 3 x 380 - 480 VAC (AF-650 GP)
AF-650 GP/AF-650 GP
High/ Normal Load*
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Typical Shaft output
[kW]
30
37
37
45
45
55
55
75
75
90
Typical Shaft Output [HP]
at 460V
40
50
50
60
60
75
75
100
100
120
Unit Size IP20
24
33
33
34
34
Unit Size IP21
31
31
31
32
32
Unit Size IP55, 66
31
31
31
32
32
Output current
Continuous
(3 x 380-440 V) [A]
61
73
73
90
90
106
106
147
147
177
Intermittent (60 sec
overload)
(3 x 380-440 V) [A]
91.5
80.3
110
99
135
117
159
162
221
195
Continuous
(3 x 441-500 V) [A]
52
65
65
80
80
105
105
130
130
160
Intermittent (60 sec
overload)
(3 x 441-500 V) [A]
78
71.5
97.5
88
120
116
158
143
195
176
Continuous KVA
(400 V AC) [KVA]
42.3
50.6
50.6
62.4
62.4
73.4
73.4
102
102
123
Continuous KVA
(460 V AC) [KVA]
51.8
63.7
83.7
104
128
Max. input current
Continuous
(3 x 380-440 V ) [A]
55
66
66
82
82
96
96
133
133
161
Intermittent (60 sec
overload)
(3 x 380-440 V ) [A]
82.5
72.6
99
90.2
123
106
144
146
200
177
Continuous
(3 x 441-500 V) [A]
47
59
59
73
73
95
95
118
118
145
Intermittent (60 sec
overload)
(3 x 441-500 V) [A]
70.5
64.9
88.5
80.3
110
105
143
130
177
160
Max. cable size IP20,
mains and motor [mm
2
(AWG
2)
)]
35 (2)
50 (1)
50 (1)
95 (4/0)
150 (300mcm)
Max. cable size IP20,
load share and brake
[mm
2
(AWG
2)
)]
35 (2)
50 (1)
50 (1)
95 (4/0)
95 (4/0)
Max. cable size,
IP21/55/66 [mm
2
(AWG
2)
)]
90 (3/0)
90 (3/0)
90 (3/0)
120 (4/0)
120 (4/0)
Max. pre-fuses [A]
1
100
125
160
250
250
Estimated power loss
at rated max. load [W]
4)
570
698
697
843
891
1083
1022
1384
1232
1474
Weight,
Unit Size IP21, IP 55, 66
[kg]
45
45
45
65
65
Efficiency
4)
0.98
0.98
0.98
0.98
0.99
* High overload = 160% torque during 60 s, Normal overload = 110% torque during 60 s
AF-650 GP Operating Instructions
73
5