Mains Supply 3 x 380 - 500 VAC (AF-650 GP), 3 x 380 - 480 VAC (AF-650 GP)
AF-650 GP/AF-650 GP
High/ Normal Load*

HO

NO

HO

NO

HO

NO

HO

NO

HO

NO

Typical Shaft output
[kW]

30

37

37

45

45

55

55

75

75

90

Typical Shaft Output [HP]
at 460V

40

50

50

60

60

75

75

100

100

120

Unit Size IP20

24

33

33

34

34

Unit Size IP21

31

31

31

32

32

Unit Size IP55, 66

31

31

31

32

32

Output current

Continuous
(3 x 380-440 V) [A]

61

73

73

90

90

106

106

147

147

177

Intermittent (60 sec
overload)
(3 x 380-440 V) [A]

91.5

80.3

110

99

135

117

159

162

221

195

Continuous
(3 x 441-500 V) [A]

52

65

65

80

80

105

105

130

130

160

Intermittent (60 sec
overload)
(3 x 441-500 V) [A]

78

71.5

97.5

88

120

116

158

143

195

176

Continuous KVA
(400 V AC) [KVA]

42.3

50.6

50.6

62.4

62.4

73.4

73.4

102

102

123

Continuous KVA
(460 V AC) [KVA]

51.8

63.7

83.7

104

128

Max. input current

Continuous
(3 x 380-440 V ) [A]

55

66

66

82

82

96

96

133

133

161

Intermittent (60 sec
overload)
(3 x 380-440 V ) [A]

82.5

72.6

99

90.2

123

106

144

146

200

177

Continuous
(3 x 441-500 V) [A]

47

59

59

73

73

95

95

118

118

145

Intermittent (60 sec
overload)
(3 x 441-500 V) [A]

70.5

64.9

88.5

80.3

110

105

143

130

177

160

Max. cable size IP20,
mains and motor [mm

2

(AWG

2)

)]

35 (2)

50 (1)

50 (1)

95 (4/0)

150 (300mcm)

Max. cable size IP20,
load share and brake
[mm

2

(AWG

2)

)]

35 (2)

50 (1)

50 (1)

95 (4/0)

95 (4/0)

Max. cable size,
IP21/55/66 [mm

2

(AWG

2)

)]

90 (3/0)

90 (3/0)

90 (3/0)

120 (4/0)

120 (4/0)

Max. pre-fuses [A]

1

100

125

160

250

250

Estimated power loss
at rated max. load [W]

4)

570

698

697

843

891

1083

1022

1384

1232

1474

Weight,
Unit Size IP21, IP 55, 66
[kg]

45

45

45

65

65

Efficiency

4)

0.98

0.98

0.98

0.98

0.99

* High overload = 160% torque during 60 s, Normal overload = 110% torque during 60 s