Af-650 gp operating instructions – GE Industrial Solutions AF-650 GP General Purpose Drive (230V to 50HP, 460_575V to 100HP) User Manual

Page 34

Advertising
background image

Unsuccessful Auto Tune

1.

The frequency converter enters into alarm mode. A description of the alarm can be found in the Warnings and Alarms chapter.

2.

"Report Value” in the [Alarm Log] shows the last measuring sequence carried out by the Auto Tune, before the frequency converter entered alarm mode.
This number along with the description of the alarm will assist you in troubleshooting. If you contact GE for service, make sure to mention number and
alarm description.

NB!
Unsuccessful Auto Tune is often caused by incorrectly entering motor name plate data or a too big difference between the motor power size and the frequency
converter power size.

Step 4. Set speed limit and accel/decel times

par. F-52 Minimum Reference
par. F-53 Maximum Reference

Table 3.3: Set up the desired limits for speed and ramp time.

par. F-18 Motor Speed Low Limit [RPM] or par. F-16 Motor Speed Low
Limit [Hz]
par. F-17 Motor Speed High Limit [RPM]
or par. F-15 Motor Speed High
Limit [Hz]

par. F-07 Accel Time 1
par. F-08 Decel Time 1

AF-650 GP Operating Instructions

33

3

Advertising