Af-650 gp operating instructions – GE Industrial Solutions AF-650 GP General Purpose Drive (230V to 50HP, 460_575V to 100HP) User Manual
Page 77
Mains Supply 3 x 525 - 600 VAC
AF-650 GP
High/ Normal
Load*
HO
NO
HO
NO
HO
NO
HO
NO
Typical Shaft Output [kW]
37
45
45
55
55
75
75
90
Typical Shaft Output [HP] at 575V
50
60
60
74
74
100
100
120
Unit Size IP21, 55, 66
31
31
31
32
32
Unit Size IP20
33
33
33
34
34
Output current
Continuous
(3 x 525-550 V ) [A]
54
65
65
87
87
105
105
137
Intermittent
(3 x 525-550 V ) [A]
81
72
98
96
131
116
158
151
Continuous
(3 x 525-600 V ) [A]
52
62
62
83
83
100
100
131
Intermittent
(3 x 525-600 V ) [A]
78
68
93
91
125
110
150
144
Continuous kVA (550 V AC) [kVA]
51.4
61.9
61.9
82.9
82.9
100.0
100.0
130.5
Continuous kVA (575 V AC) [kVA]
51.8
61.7
61.7
82.7
82.7
99.6
99.6
130.5
Max. cable size IP20
(mains, motor)
[AWG]
2)
[mm
2
]
50 (1)
95 (4/0)
150 (300mcm)
Max. cable size IP20
(load share, brake)
[AWG]
2)
[mm
2
]
50 (1)
95 (4/0)
Max. cable size IP21, 55, 66
(mains, motor, load share and
brake)
[AWG]
2)
[mm
2
]
90 (3/0)
120 (4/0)
Max. input current
Continuous
at 550 V [A]
49
59
59
78.9
78.9
95.3
95.3
124.3
Intermittent
at 550 V [A]
74
65
89
87
118
105
143
137
Continuous
at 575 V [A]
47
56
56
75
75
91
91
119
Intermittent
at 575 V [A]
70
62
85
83
113
100
137
131
Max. pre-fuses
1)
[A]
125
160
250
250
Environment
Estimated power loss
at rated max. load [W]
4)
850
1100
1400
1500
Weight,
Unit Size IP20 [kg]
35
35
50
50
Weight,
Unit Size IP21, 55 [kg]
45
45
65
65
Efficiency
4)
0.98
0.98
0.98
0.98
AF-650 GP Operating Instructions
76
5