Mains Supply 3 x 525 - 600 VAC
AF-650 GP
High/ Normal
Load*

HO

NO

HO

NO

HO

NO

HO

NO

Typical Shaft Output [kW]

37

45

45

55

55

75

75

90

Typical Shaft Output [HP] at 575V

50

60

60

74

74

100

100

120

Unit Size IP21, 55, 66

31

31

31

32

32

Unit Size IP20

33

33

33

34

34

Output current

Continuous
(3 x 525-550 V ) [A]

54

65

65

87

87

105

105

137

Intermittent
(3 x 525-550 V ) [A]

81

72

98

96

131

116

158

151

Continuous
(3 x 525-600 V ) [A]

52

62

62

83

83

100

100

131

Intermittent
(3 x 525-600 V ) [A]

78

68

93

91

125

110

150

144

Continuous kVA (550 V AC) [kVA]

51.4

61.9

61.9

82.9

82.9

100.0

100.0

130.5

Continuous kVA (575 V AC) [kVA]

51.8

61.7

61.7

82.7

82.7

99.6

99.6

130.5

Max. cable size IP20
(mains, motor)
[AWG]

2)

[mm

2

]

50 (1)

95 (4/0)

150 (300mcm)

Max. cable size IP20
(load share, brake)
[AWG]

2)

[mm

2

]

50 (1)

95 (4/0)

Max. cable size IP21, 55, 66
(mains, motor, load share and
brake)
[AWG]

2)

[mm

2

]

90 (3/0)

120 (4/0)

Max. input current

Continuous
at 550 V [A]

49

59

59

78.9

78.9

95.3

95.3

124.3

Intermittent
at 550 V [A]

74

65

89

87

118

105

143

137

Continuous
at 575 V [A]

47

56

56

75

75

91

91

119

Intermittent
at 575 V [A]

70

62

85

83

113

100

137

131

Max. pre-fuses

1)

[A]

125

160

250

250

Environment
Estimated power loss
at rated max. load [W]

4)

850

1100

1400

1500

Weight,
Unit Size IP20 [kg]

35

35

50

50

Weight,
Unit Size IP21, 55 [kg]

45

45

65

65

Efficiency

4)

0.98

0.98

0.98

0.98

AF-650 GP Operating Instructions

76

5

Advertising