3.3.4 Fuses

Branch circuit protection:

In order to protect the installation against electrical and fire hazard, all branch circuits in an installation, switch gear, machines etc., must be short-circuited and
overcurrent protected according to national/international regulations.

Short-circuit protection:

The frequency converter must be protected against short-circuit to avoid electrical or fire hazard. GE recommends using the fuses mentioned below to protect
service personnel and equipment in case of an internal failure in the drive. The frequency converter provides full short-circuit protection in case of a short-circuit
on the motor output.

Overcurrent protection:

Provide overload protection to avoid fire hazard due to overheating of the cables in the installation. Fuses or circuit breakers can be used to provide the overcurrent
protection in the installation. Overcurrent protection must always be carried out according to national regulations.

The AF-650 GP drive is suitable in a circuit capable of supplying a maximum of 100,000 A

rms

(symmetrical), 500 V maximum.

Non UL compliance

If UL/cUL is not to be complied with, we recommend using the following fuses, which will ensure compliance with EN50178:
In case of malfunction, not following the recommendation may result in unnecessary damage to the frequency converter.

AF-650 GP

Max. fuse size

1)

Voltage

Type

1/3 to 1 HP

10A

200-240 V

type gG

2 to 3 HP

20A

200-240 V

type gG

5 HP

32A

200-240 V

type gG

7.5 to 10 HP

63A

380-500 V

type gG

15 HP

80A

380-500 V

type gG

20 to 25 HP

125A

380-500 V

type gG

30 HP

160A

380-500 V

type aR

40 HP

200A

380-500 V

type aR

50 HP

250A

380-500 V

type aR

1) Max. fuses - refer to national/international regulations to select an appropriate fuse size.

AF-650 GP

Max. fuse size

1)

Voltage

Type

3 to 5 HP

10A

380-500 V

type gG

3 to 5 HP

20A

380-500 V

type gG

7.5 to 10 HP

32A

380-500 V

type gG

15 to 25 HP

63A

380-500 V

type gG

30 HP

80A

380-500 V

type gG

40 HP

100A

380-500 V

type gG

50 HP

125A

380-500 V

type gG

60 HP

160A

380-500 V

type aR

75 to 100 HP

250A

380-500 V

type aR

AF-650 GP Operating Instructions