Af-650 gp operating instructions – GE Industrial Solutions AF-650 GP General Purpose Drive (230V to 50HP, 460_575V to 100HP) User Manual
Page 71
Mains Supply 3 x 200- 240 VAC
AF-650 GP/AF-650
GP
High/ Normal Load*
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Typical Shaft Output [kW]
15
18.5
18.5
22
22
30
30
37
37
45
Typical Shaft Output [HP]
at 208 V
20
25
25
30
30
40
40
50
50
60
Unit Size IP20
24
33
33
34
34
Unit Size IP21
31
31
31
32
32
Unit Size IP55, 66
31
31
31
32
32
Output current
Continuous
(3 x 200-240 V) [A]
59.4
74.8
74.8
88
88
115
115
143
143
170
Intermittent
(60 sec overload)
(3 x 200-240 V) [A]
89.1
82.3
112
96.8
132
127
173
157
215
187
Continuous
KVA (208 V AC) [KVA]
21.4
26.9
26.9
31.7
31.7
41.4
41.4
51.5
51.5
61.2
Max. input current
Continuous
(3 x 200-240 V ) [A]
54
68
68
80
80
104
104
130
130
154
Intermittent
(60 sec overload)
(3 x 200-240 V ) [A]
81
74.8
102
88
120
114
156
143
195
169
Max. cable size, IP20
[mm
2
(AWG)]
2)
35 (2)
90 (3/0)
90 (3/0)
120 (4/0)
120 (4/0)
Max. cable size, IP
21/55/66 [mm
2
(AWG)]
2)
90 (3/0)
90 (3/0)
90 (3/0)
120 (4/0)
120 (4/0)
Max. pre-fuses [A]
1
125
125
160
200
250
Estimated power loss
at rated max. load [W]
4)
624
737
740
845
874
1140
1143
1353
1400
1636
Weight,
Unit Size IP21, IP 55, 66 [kg]
45
45
45
65
65
Efficiency
4)
0.96
0.97
0.97
0.97
0.97
* High overload = 160% torque during 60 s, Normal overload = 110% torque during 60 s
AF-650 GP Operating Instructions
70
5