Af-650 gp operating instructions – GE Industrial Solutions AF-650 GP General Purpose Drive (230V to 50HP, 460_575V to 100HP) User Manual

Page 71

Advertising
background image

Mains Supply 3 x 200- 240 VAC
AF-650 GP/AF-650
GP
High/ Normal Load*

HO

NO

HO

NO

HO

NO

HO

NO

HO

NO

Typical Shaft Output [kW]

15

18.5

18.5

22

22

30

30

37

37

45

Typical Shaft Output [HP]
at 208 V

20

25

25

30

30

40

40

50

50

60

Unit Size IP20

24

33

33

34

34

Unit Size IP21

31

31

31

32

32

Unit Size IP55, 66

31

31

31

32

32

Output current

Continuous
(3 x 200-240 V) [A]

59.4

74.8

74.8

88

88

115

115

143

143

170

Intermittent
(60 sec overload)
(3 x 200-240 V) [A]

89.1

82.3

112

96.8

132

127

173

157

215

187

Continuous
KVA (208 V AC) [KVA]

21.4

26.9

26.9

31.7

31.7

41.4

41.4

51.5

51.5

61.2

Max. input current

Continuous
(3 x 200-240 V ) [A]

54

68

68

80

80

104

104

130

130

154

Intermittent
(60 sec overload)
(3 x 200-240 V ) [A]

81

74.8

102

88

120

114

156

143

195

169

Max. cable size, IP20
[mm

2

(AWG)]

2)

35 (2)

90 (3/0)

90 (3/0)

120 (4/0)

120 (4/0)

Max. cable size, IP
21/55/66 [mm

2

(AWG)]

2)

90 (3/0)

90 (3/0)

90 (3/0)

120 (4/0)

120 (4/0)

Max. pre-fuses [A]

1

125

125

160

200

250

Estimated power loss
at rated max. load [W]

4)

624

737

740

845

874

1140

1143

1353

1400

1636

Weight,
Unit Size IP21, IP 55, 66 [kg]

45

45

45

65

65

Efficiency

4)

0.96

0.97

0.97

0.97

0.97

* High overload = 160% torque during 60 s, Normal overload = 110% torque during 60 s