5 general specifications, Af-650 gp operating instructions – GE Industrial Solutions AF-650 GP General Purpose Drive (230V to 50HP, 460_575V to 100HP) User Manual

Page 70

Advertising
background image

5 General Specifications

5.1 Electrical Data - 200-240 V

Mains Supply 3 x 200 - 240 VAC
AF-650 GP/AF-650 GP

Typical Shaft Output [kW]

0.25

0.37

0.55

0.75

1.1

1.5

2.2

3

3.7

Typical Shaft Output [HP] at 208 V

0.3

0.5

0.7

1.0

1.5

2.0

2.9

4.0

4.9

Unit Size IP 20/IP 21

12

12

12

12

12

12

12

13

13

Unit Size IP 20 (AF-650 GP only)

11

11

11

11

11

11

-

-

-

Unit Size IP 55, 66

15

15

15

15

15

15

15

15

15

Output current

Continuous
(3 x 200-240 V ) [A]

1.8

2.4

3.5

4.6

6.6

7.5

10.6

12.5

16.7

Intermittent
(3 x 200-240 V ) [A]

2.9

3.8

5.6

7.4

10.6

12.0

17.0

20.0

26.7

Continuous
KVA (208 V AC) [KVA]

0.65

0.86

1.26

1.66

2.38

2.70

3.82

4.50

6.00

Max. cable size (mains, motor,
brake) [mm

2

(AWG

2)

)]

0.2 - 4 (24 - 10)

Max. input current

Continuous
(3 x 200-240 V ) [A]

1.6

2.2

3.2

4.1

5.9

6.8

9.5

11.3

15.0

Intermittent
(3 x 200-240 V ) [A]

2.6

3.5

5.1

6.6

9.4

10.9

15.2

18.1

24.0

Max. pre-fuses

1)

[A]

10

10

10

10

20

20

20

32

32

Environment
Estimated power loss
at rated max. load [W]

4)

21

29

42

54

63

82

116

155

185

Weight, Unit Size IP20 [kg]

4.7

4.7

4.8

4.8

4.9

4.9

4.9

6.6

6.6

11 (IP20)

2.7

2.7

2.7

2.7

2.7

2.7

-

-

-

15 (IP55, 66)

13.5

13.5

13.5

13.5

13.5

13.5

13.5

13.5

13.5

Efficiency

4)

0.94

0.94

0.95

0.95

0.96

0.96

0.96

0.96

0.96

0.25 - 3.7 kW only available as 160% high overload.

Mains Supply 3 x 200- 240 VAC
AF-650 GP/AF-650 GP
High/ Normal Load*

HO

NO

HO

NO

HO

NO

Typical Shaft Output [kW]

5.5

7.5

7.5

11

11

15

Typical Shaft Output [HP] at 208 V

7.5

10

10

15

15

20

Unit Size IP20

23

23

24

Unit Size IP21

21

21

22

Unit Size IP55, 66

21

21

22

Output current

Continuous
(3 x 200-240 V) [A]

24.2

30.8

30.8

46.2

46.2

59.4

Intermittent
(60 sec overload)
(3 x 200-240 V) [A]

38.7

33.9

49.3

50.8

73.9

65.3

Continuous
KVA (208 V AC) [KVA]

8.7

11.1

11.1

16.6

16.6

21.4

Max. input current

Continuous
(3 x 200-240 V ) [A]

22

28

28

42

42

54

Intermittent
(60 sec overload)
(3 x 200-240 V ) [A]

35.2

30.8

44.8

46.2

67.2

59.4

Max. cable size [mm

2

(AWG)]

2)

16 (6)

16 (6)

35 (2)

Max. pre-fuses [A]

1

63

63

80

Estimated power loss
at rated max. load [W]

4)

239

310

371

514

463

602

Weight,
Unit Size IP21, IP 55, 66 [kg]

23

23

27

Efficiency

4)

0.964

0.959

0.964

* High overload = 160% torque during 60 s, Normal overload = 110% torque during 60 s

AF-650 GP Operating Instructions

69

5

Advertising