GE Industrial Solutions AF-650 GP PROFINET User Manual

Page 21

Advertising
background image

Illustration 5.5

The configuration tool automatically assigns addresses in the peripheral address area. In this example the input and output
area have the following configuration:

PPO type 6:

PCD word number

0

1

2

3

Input address

256-257

258-259

260-261

262-263

Set-up

STW

MAV

PB-16 PCD Read Configuration.2

PB-16 PCD Read Configuration.3

Table 5.1 PCD Read (Drive to PLC)

PCD word number

0

1

2

3

Output address

256-257

258-259

260-261

262-263

Set-up

CTW

MRV

PB-15 PCD Write Configuration.2

PB-15 PCD Write Configuration.3

Table 5.2 PCD Write (PLC to Drive)

The PCDs have to be assigned via PB-16 PCD Read Configuration for inputs and PB-15 PCD Write Configuration for outputs.

Download the configuration file to the PLC. The PROFINET system should be able to go online and it will start to exchange
data when the PLC is set to Run mode.

How to Configure the System

PROFINET Operating Instruction

20

5