5.3 Configure the Frequency Converter

5.3.1 Drive Parameters

Pay particular attention to the following parameters when
configuring the frequency converter with a PROFINET
interface.

K-40 [Hand] Button on Keypad. If the Hand button
on the frequency converter is activated, control of
the drive via the PROFINET interface is disabled

After an initial power up the frequency converter
will automatically detect whether a network
option is installed in slot A, and set O-02 Control
Word Source
to [Option A]. If an option is added,
changed or removed from an already commis-
sioned drive, it will not change O-02 Control Word
Source
but enter Trip Mode, and the drive will
display an error

O-10 Control Word Profile. Choose between the GE
Drive Profile and the PROFIdrive profile

O-50 Coasting Select to O-56 Preset Reference
Select
. Selection of how to gate PROFINET control
commands with digital input command of the
control module.

NOTE

When O-01 Control Site is set to [2] Control word only, then
the settings in O-50 Coasting Select to O-56 Preset Reference
Select
will be overruled, and all act on Bus-control.

O-03 Control Word Timeout Time to O-05 End-of-
Timeout Function
. The reaction in the event of a
network time out is set via these parameters

EN-00 IP Address Assignment

EN-08 Host Name

How to Configure the System

PROFINET Operating Instruction

21