Depending on the setting of F-50 Reference Range the reference and MAV are scaled accordingly:

Illustration 6.2

NOTE

If F-50 Reference Range is set to [0] Min - Max, a negative reference will be handled as 0%.

The actual output of the frequency converter is limited by the speed limit parameters in F-18 Motor Speed Low Limit [RPM]
to F-15 Motor Speed High Limit [Hz].
The final speed limit is set by F-03 Max Output Frequency 1.

The reference and the MAV have the format which appears
from the table

MRV / MAV

Integer in hex

Integer in decimal

100%

4000

16.384

75%

3000

12.288

50%

2000

8.192

25%

1000

4.096

0%

0

0

-25%

F000

-4.096

-50%

E000

-8.192

-75%

D000

-12.288

-100%

C000

-16.384

Table 6.4

NOTE

Negative numbers are formed as two's complement.

NOTE

The data type for MRV and MAV is a N2 16 bit
standardised value, meaning it can express a range from
-200% to +200% (8001 to 7FFF).

H-40 Configuration Mode set to [0] Speed open loop.
F-50 Reference Range set to [0] Min - Max.
F-52 Minimum Reference set to 100 RPM.
F-53 Maximum Reference set to 3000 RPM.

MRV / MAV

Actual Speed

0%

0 hex

100 RPM

25%

1000 hex

825 RPM

50%

2000 hex

1550 RPM

75%

3000 hex

2275 RPM

100%

4000 hex

3000 RPM

Table 6.5

6.2.4 Process Control Operation

In process control operation H-40 Configuration Mode is set
to [3] Process.
The reference range in F-50 Reference Range is alway [0]
Min - Max.
- MRV represents the process setpoint.
- MAV expresses the actual process feedback (range +/-
200%).

How to Control the Frequenc...

PROFINET Operating Instruction

24