9.2 E.g.: Control Word Network using Standard Telegram 1 / PPO3

This example shows how the control word network relates to the controller and the frequency converter, using GE Drive
Control Profile.

The control word network is sent from the PLC to the frequency converter. Standard Telegram 1 is used in the example in
order to demonstrate the full range of modules. All the values shown are arbitrary, and are provided for the purposes of
demonstration only.

PCD

0

1

2

3

CTW

MRV

PCD

PCD

04

7C

20

00

PQW:

256

258

260

262

CTW

MRV

Bit no.:

31

30

29

28

27

26

25

24

23

22

21

20

19

18

17

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

0

0

0

0

1

0

0

0

1

1

1

1

1

0

0

0

0

1

0

0

0

0

0

0

0

0

0

0

0

0

0

0

4

7

C

2

0

0

0

Table 9.3

Table 9.3 indicates the bits contained within the control word, and how they are presented as process data in Standard
Telegram 1 for this example.

Table 9.4 indicates which bit functions, and which corresponding bit values are active for this example.

Bit

Bit value = 0

Bit value = 1

Bit value

00

Reference value

External selection lsb

0

C

01

Reference value

External selection msb

0

02

DC brake

Accel/Decel

1

03

Coasting

Enable

1

04

Quick stop

Accel/Decel

1

7

05

Freeze output

Accel/Decel enable

1

06

Accel/Decel stop

Start

1

07

No function

Reset

0

08

No function

Jog

0

4

09

Accel/Decel 1

Accel/Decel 2

0

10

Data not valid

Valid

1

11

No function

Relay 01 active

0

12

No function

Relay 02 active

0

0

13

Parameter set-up

Selection lsb

0

14

Parameter set-up

Selection msb

0

15

No function

Reversing

0

Function

active

Function

inactive

Table 9.4