EN-06 Name Servers

Range:

Function:

0 N/A

*

[0 - 2147483647 N/A] IP addresses of Domain Name

Servers. Can be automatically

assigned when using DHCP.

EN-07 Domain Name

Range:

Function:

0 N/A [0 - 2147483647 N/A] Domain name of the attached

network. Can be automatically

assigned when using DHCP.

EN-08 Host Name

Range:

Function:

0 N/A

[0 - 0 N/A]

Logical (given) name of option.

NOTE

Please note that the display of the drive will only show the
first 19 characters, but the remaining characters are stored
in the drive.

EN-09 Physical Address

Range:

Function:

0 N/A

*

[0 - 0 N/A] Read only Displays the Physical (MAC)

address of the option.

EN-1# Ethernet Link parameters

Option:

Function:

Applies for whole parameter group.

[0]

Port 1

[1]

Port 2

EN-10 Link Status

Option:

Function:

Read only. Displays the link status of the Ethernet

ports.

[0]

*

No Link

[1]

Link

EN-11 Link Duration

Range:

Function:

0 N/A

*

[0 - 0 N/A] Read only. Displays the duration of the

present link on each port in dd:hh:mm:ss.

EN-12 Auto Negotiation

Option:

Function:

Configures Auto Negotiation of Ethernet link

parameters, for each port: ON or OFF.

[0]

Off

Link Speed and Link Duplex can be configured in

EN-13 Link Speed and EN-14 Link Duplex.

[1]

*

On

NOTE

It is recommended to set EN-12 Auto Negotiation to OFF [0]
for the PROFINET option and for the connected port. This
will ensure that the connected ports will be set to an
optimized Link Speed with Link Duplex setting. If only one
of the ports in a link is set to Auto Negotiation ON, it can
course the ports to switch to half duplex, resulting in poor
network performance. Most switches today have Auto
negotiation set, but this can lead to a longer time to
establish a connection.

EN-13 Link Speed

Option:

Function:

Forces the link speed for each port in 10 or 100

Mbps. If EN-12 Auto Negotiation is set to: ON,

this parameter is read only and displays the

actual link speed. “None” is displayed if no link

is present.

[0]

*

None

[1]

10 Mbps

[2]

*

100 Mbps

EN-14 Link Duplex

Option:

Function:

Forces the duplex for each port to Full or Half

duplex. If EN-12 Auto Negotiation is set to: ON,

this parameter is read only.

[0]

Half Duplex

[1]

*

Full Duplex

EN-80 FTP Server

Option:

Function:

[0]

*

Disabled

Disables the built-in FTP server.

[1]

Enabled

Enables the built-in FTP server.

EN-81 HTTP Server

Option:

Function:

[0]

*

Disabled

Disables the built-in HTTP (web) server.

[1]

Enabled

Enables the built-in HTTP (web) server.

EN-82 SMTP Service

Option:

Function:

[0]

*

Disabled Disables the SMTP (e-mail) service on the option.

[1]

Enabled

Enables the SMTP (e-mail) service on the option.

EN-89 Transparent Socket Channel Port

Range:

Function:

4000

N/A

*

[0 - 65535

N/A]

Configures the TCP port number for

the transparent socket channel. This

enables Drive messages to be sent

transparently on Ethernet via TCP.

Default value is 4000, 0 means