8.4 PROFINET-specific

Parameter

List

Parameter

Default value

Range

Conver-
sion index

Data type

O-01 Control Site

Dig. & ctrl. word [0]

[0 - 2]

-

Uint8

O-02 Control Word Source

Drive RS485 [0]

[0 - 4]

-

Uint8

O-03 Control Word Timeout Time

1

0.1-18000

-1

Uint32

O-04 Control Word Timeout Function

Off [0]

[0 - 10]

-

Uint8

O-05 End-of-Timeout Function

Hold set-up [0]

[0 - 1]

-

Uint8

O-06 Reset Control Word Timeout

Do not reset [0]

[0 - 1]

-

Uint8

O-07 Diagnosis Trigger

Disable [0]

[0 - 3]

-

Uint8

O-10 Control Word Profile

GE Drive profile [0]

[0 - x]

-

Uint8

O-13 Configurable Status Word STW

O-50 Coasting Select

*Logic OR [3]

[0 - 3]

-

Uint8

O-51 Quick Stop Select

*Logic OR [3]

[0 - 3]

-

Uint8

O-52 DC Brake Select

*Logic OR [3]

[0 - 3]

-

Uint8

O-53 Start Select

*Logic OR [3]

[0 - 3]

-

Uint8

O-54 Reversing Select

*Logic OR [3]

[0 - 3]

-

Uint8

O-55 Set-up Select

*Logic OR [3]

[0 - 3]

-

Uint8

O-56 Preset Reference Select

*Logic OR [3]

[0 - 3]

-

Uint8

O-90 Bus Jog 1 Speed

100 rpm

0 - F-17 Motor Speed High

Limit [RPM]

67

Uint16

O-91 Bus Jog 2 Speed

200 rpm

0 - F-17 Motor Speed High

Limit [RPM]

67

Uint16

PB-15 PCD Write Configuration

-

-

-

Uint16

PB-16 PCD Read Configuration

-

-

-

Uint16

PB-22 Telegram Selection

-

[0 - 108]

-

Uint8

PB-23 Parameters for Signals

-

0 - 573

-

Uint16

PB-27 Parameter Edit

Enabled [1]

[0 - 1]

-

Uint16

PB-28 Process Control

Enable cyclic master [1]

[0 - 1]

-

Uint16

PB-44 Fault Message Counter

0

[0 - 8]

0

Uint16

PB-45 Fault Code

0

-

-

Uint16

PB-47 Fault Number

0

-

-

Uint16

PB-52 Fault Situation Counter

0

0 - 1000

0

Uint16

PB-53 Profibus Warning Word

0

16 bits

0

V2

PB-64 Device Identification

0

[0 - 10]

0

Uint16

PB-65 Profile Number

0

8 bits

0

Uint8

PB-70 Edit Set-up

Active set-up [9]

[0 - 9]

-

Uint8

PB-71 Profibus Save Data Values

Off [0]

[0 - 2]

-

Uint8

PB-72 ProfibusDriveReset

No action [0]

[0 - 2]

-

Uint8

PB-80 Defined Parameters (1)

-

0-115

0

Uint16

PB-81 Defined Parameters (2)

0-115

0

Uint16

PB-82 Defined Parameters (3)

-

0-115

0

Uint16

PB-83 Defined Parameters (4)

-

0-115

0

Uint16

PB-90 Changed Parameters (1)

-

0-115

0

Uint16

PB-91 Changed Parameters (2)

-

0-115

0

Uint16

PB-92 Changed Parameters (3)

-

0-115

0

Uint16

PB-93 Changed parameters (4)

-

0-115

0

Uint16

EN-00 IP Address Assignment

0.0.0.0

0 - 255

-

Unsigned 8

EN-01 IP Address

0.0.0.0

0 - 255

-

Oct. string 4

EN-02 Subnet Mask

0.0.0.0

0 - 255

-

Oct. string 4

EN-03 Default Gateway

0.0.0.0

0 - 255

-

Oct. string 4-

EN-04 DHCP Server

0.0.0.0

0 - 255

-

Oct. string 4

Parameters

PROFINET Operating Instruction

45

8