8.1 Parameter Group O-## Communication and Option

O-01 Control Site

Option:

Function:

The setting in this parameter overrides

the settings in O-50 Coasting Select to

O-56 Preset Reference Select.

[0]

*

Digital and

ctrl.word

Control by using both digital input and

control word.

[1]

Digital only

Control by using digital inputs only.

[2]

Controlword only

Control by using control word only.

O-03 Control Word Timeout Time

Range:

Function:

1.0 s

*

[0.1 -

18000.0 s]

Enter the maximum time expected to pass

between the reception of two consecutive

messages. If this time is exceeded, it

indicates that the serial communication has

stopped. The function selected in

O-04 Control Word Timeout Function will

then be carried out. The time-out counter is

triggered by a valid control word.

O-04 Control Word Timeout Function

Select the time-out function. The time-out function activates

when the control word fails to be updated within the time

period specified in O-03 Control Word Timeout Time.

Option:

Function:

[0]

*

Off

Resumes control via serial bus (network or

standard) using the most recent control

word.

[1]

Freeze output Freezes output frequency until communi-

cation resumes.

[2]

Stop

Stops with auto restart when communi-

cation resumes.

[3]

Jogging

Runs the motor at JOG frequency until

communication resumes.

[4]

Max. speed

Runs the motor at maximum frequency

until communication resumes.

[5]

Stop and trip

Stops the motor, then resets the drive in

order to restart: via the network, via the

reset button on the keypad or via a digital

input.

[7]

Select setup 1 Changes the set-up upon reestablishment of

communication following a control word

time-out. If communication resumes causing

the time-out situation to disappear,

O-05 End-of-Timeout Function defines

whether to resume the set-up used before

O-04 Control Word Timeout Function

Select the time-out function. The time-out function activates

when the control word fails to be updated within the time

period specified in O-03 Control Word Timeout Time.

Option:

Function:

the time-out or to retain the set-up

endorsed by the time-out function.

[8]

Select setup 2 See [7] Select setup 1

[9]

Select setup 3 See [7] Select setup 1

[10]

Select setup 4 See [7] Select setup 1

[26]

Trip

NOTE

The following configuration is required in order to change
the set-up after a time-out:
Set K-10 Active Set-up to [9] Multi set-up and select the
relevant link in K-12 This Set-up Linked to.

O-05 End-of-Timeout Function

Option:

Function:

Select the action after receiving a valid

control word following a time-out. This

parameter is active only when O-04 Control

Word Timeout Function is set to [Set-up 1-4].

[0]

Hold set-up

Retains the set-up selected in O-04 Control

Word Timeout Function and displays a

warning, until O-06 Reset Control Word

Timeout toggles. Then the drive resumes its

original set-up.

[1]

*

Resume set-

up

Resumes the set-up active prior to the time-

out.

O-06 Reset Control Word Timeout

This parameter is active only when Hold set-up [0] has been

selected in O-05 End-of-Timeout Function.

Option:

Function:

[0]

*

Do not reset Retains the set-up specified in O-04 Control

Word Timeout Function, following a control

word time-out.

[1]

Do reset

Returns the drive to the original set-up

following a control word time-out. The drive

performs the reset and then immediately

reverts to the Do not reset [0] setting

Parameters