GE Industrial Solutions AF-650 GP PROFINET User Manual

Page 53

Advertising
background image

9.3 E.g.: Status Word Network using Standard Telegram 1 / PPO3

This example shows how the control word network relates to the PLC and the frequency converter, using GE Drive Control
Profile.

The control word network is sent from the frequency converter to the controller. Standard Telegram 1 is used in the
example in order to demonstrate the full range of modules. All the values shown are arbitrary, and are provided for the
purposes of demonstration only.

PCD

0

1

2

3

STW

MAV

PCD

PCD

0F

07

20

00

PIW:

256

258

260

262

STW

MAV

Bit no.:

31

30

29

28

27

26

25

24

23

22

21

20

19

18

17

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

0

0

0

0

1

0

0

0

1

1

1

1

1

0

0

0

0

1

0

0

0

0

0

0

0

0

0

0

0

0

0

0

F

0

7

2

0

0

0

Table 9.5

Table 9.5 indicates the bits contained within the status word, and how they are presented as process data in Standard
Telegram 1 for this example.

Table 9.6 indicates which bit functions, and which corresponding bit values are active for this example.

Bit

Bit value = 0

Bit value = 1

Bit value

00

Control not ready

Control ready

1

7

01

Drive not ready

Drive ready

1

02

Coasting

Enable

1

03

No error

Trip

0

04

No error

Error (no trip)

0

0

05

Reserved

-

0

06

No error

Triplock

0

07

No warning

Warning

0

08

Speed reference

Speed = reference

1

F

09

Local operation

Network control

1

10

Outside frequency range

Within frequency range

1

11

No operation

In operation

1

12

Drive ok

Stopped, autostart

0

0

13

Voltage ok

Voltage exceeded

0

14

Torque ok

Torque exceeded

0

15

Timers ok

Timers exceeded

0

Function

active

Function

inactive

Table 9.6

Application Examples

PROFINET Operating Instruction

52

9

9

Advertising