GE Industrial Solutions AF-650 GP PROFINET User Manual
Page 51
Advertising
Program the frequency converter as follows:
Parameter
Setting
H-08 Reverse Lock
Both directions [2]
E-01 Terminal 18 Digital Input
No operation [0]
E-02 Terminal 19 Digital Input
Reversing [10]
E-24 Function Relay
Control word bit 11/12 [36/37]
O-03 Control Word Timeout Time
1 sec
O-04 Control Word Timeout Function
Stop [2]
O-10 Control Word Profile
GE Drive Profile [0]
O-50 Coasting Select
Network [1]
O-51 Quick Stop Select
Network [1]
O-52 DC Brake Select
Network [1]
O-53 Start Select
Network [1]
O-54 Reversing Select
Logic AND [2]
O-55 Set-up Select
Network [1]
O-56 Preset Reference Select
Network [1]
PB-16 PCD Read Configuration
Sub index [2] DR-16 Torque [Nm]
Sub indes [3] DR-60 Digital Input
Table 9.2
Application Examples
PROFINET Operating Instruction
50