Program the frequency converter as follows:

Parameter

Setting

H-08 Reverse Lock

Both directions [2]

E-01 Terminal 18 Digital Input

No operation [0]

E-02 Terminal 19 Digital Input

Reversing [10]

E-24 Function Relay

Control word bit 11/12 [36/37]

O-03 Control Word Timeout Time

1 sec

O-04 Control Word Timeout Function

Stop [2]

O-10 Control Word Profile

GE Drive Profile [0]

O-50 Coasting Select

Network [1]

O-51 Quick Stop Select

Network [1]

O-52 DC Brake Select

Network [1]

O-53 Start Select

Network [1]

O-54 Reversing Select

Logic AND [2]

O-55 Set-up Select

Network [1]

O-56 Preset Reference Select

Network [1]

PB-16 PCD Read Configuration

Sub index [2] DR-16 Torque [Nm]

Sub indes [3] DR-60 Digital Input

Table 9.2

Application Examples

PROFINET Operating Instruction