4 will not respond to control signals – GE Industrial Solutions AF-650 GP PROFINET User Manual

Page 58

Advertising
background image

10.1.3 Warning 34 Appears even though

Communication is Established

If the master is in stop mode Warning 34 will appear.
Check that the master is in run mode.

10.1.4 Will Not Respond to Control Signals

Check 1: Is the Control word valid?
If bit 10=0 in the Control word, the drive will not accept
the Control word.

Check 2: Is the relationship between bits in the Control
word and the terminal I/Os correct?
Check the logical relationship in the drive.

Define the desired logical relationship in O-50 Coasting
Select
to O-56 Preset Reference Select according to the
following range of options. Select the Drive control mode,
digital input and/or serial communication, using
O-50 Coasting Select to O-56 Preset Reference Select.

The tables below show the effect upon the frequency
converter of a coast command for the full range of
O-50 Coasting Select settings.

The effect of control mode upon the function of
O-50 Coasting Select, O-51 Quick Stop Select and O-52 DC
Brake Select
is as follows:

If Digital input [0] is selected, the terminals will control the
Coast and DC Brake functions.

NOTE

Please note that Coasting, Quick Stop and DC brake
functions are active for logic 0.

Digital input [0]

Terminal

Bit 02/03/04

Function

0

0

Coast/DC brake/Q-Stop

0

1

Coast/DC brake/Q-Stop

1

0

No Coast/DC brake/Q-Stop

1

1

No Coast/DC brake/Q-Stop

Table 10.4

If Serial communication [1] is selected, commands will be
activated only when given via serial communication.

Serial communication [1]

Terminal

Bit 02/03/04

Function

0

0

Coast/DC brake/Q-Stop

0

1

No Coast/DC brake/Q-Stop

1

0

Coast/DC brake/Q-Stop

1

1

No Coast/DC brake/Q-Stop

Table 10.5

If Logic AND [2] is selected, both signals must be activated
to perform the function.

Logic AND [2]

Terminal

Bit 02/03/04

Function

0

0

Coast/DC brake/Q-Stop

0

1

No Coast/DC brake/Q-Stop

1

0

No Coast/DC brake/Q-Stop

1

1

No Coast/DC brake/Q-Stop

Table 10.6

If Logic OR [3] is selected, activation of one signal will
activate the function.

Logic OR [3]

Terminal

Bit 02/03/04

Function

0

0

Coast/DC brake/Q-Stop

0

1

Coast/DC brake/Q-Stop

1

0

Coast/DC brake/Q-Stop

1

1

No Coast/DC brake/Q-Stop

Table 10.7

The effect of control mode upon the function of O-53 Start
Select
and O-54 Reversing Select:

If Digital input [0] is selected, the terminals will control the
start and reversing functions

Digital input [0]

Terminal

Bit 06/15

Function

0

0

Stop/Anti-clockwise

0

1

Stop/Anti-clockwise

1

0

Start/Clockwise

1

1

Start/Clockwise

Table 10.8

If Serial communication [1] is selected, commands will be
activated only when given via serial communication.

Troubleshooting

PROFINET Operating Instruction

57

10

10

Advertising