O-90 Bus Jog 1 Speed

Range:

Function:

100 RPM

*

[0 - par. F-17

RPM]

Enter the jog speed. This is a fixed

jog speed activated via the serial

port or network option.

O-91 Bus Jog 2 Speed

Range:

Function:

200 RPM

*

[0 - par. F-17

RPM]

Enter the jog speed. This is a fixed

jog speed activated via the serial

port or network option.

8.2 Parameter Group PB-## PROFIdrive

PB-15 PCD Write Configuration

Array [10]

Option: Function:

Select the parameters to be assigned to PCD 3 to 10 of

the messages. The number of available PCDs depends

on the telegram type. The values in PCD 3 to 10 will

then be written to the selected parameters as data

values. Alternatively, specify a standard Profibus

message in PB-22 Telegram Selection.

PB-16 PCD Read Configuration

Array [10]

Option: Function:

Select the parameters to be assigned to PCD 3 to 10 of

the messages. The number of available PCDs depends

on the telegram type. PCDs 3 to 10 contain the actual

data values of the selected parameters. For standard

Profibus message, see PB-22 Telegram Selection.

PB-22 Telegram Selection

Option:

Function:

Select a standard Profibus telegram

configuration for the frequency

converter, as an alternative to

using the freely configurable

telegrams in PB-15 PCD Write

Configuration and PB-16 PCD Read

Configuration.

[1]

Standard telegram 1

[100]

None

[101]

PPO 1

[102]

PPO 2

[103]

PPO 3

[104]

PPO 4

[105]

PPO 5

[106]

PPO 6

[107]

PPO 7

[108]

*

PPO 8

[200]

Custom telegram 1

[202]

Custom telegram 3

PB-23 Parameters for Signals

Array [1000]

Option: Function:

This parameter contains a list of signals available for

selection in PB-15 PCD Write Configuration and

PB-16 PCD Read Configuration.

PB-27 Parameter Edit

Option:

Function:

Parameters can be edited via PROFINET, the

standard RS485 interface, or the keypad.

[0]

Disabled Disables editing via PROFINET.

[1]

*

Enabled

Enables editing via PROFINET.

PB-28 Process Control

Option:

Function:

Process control (setting of Control Word, speed

reference, and process data) is possible via

either PROFINET or standard Network but not

both simultaneously. Local control is always

possible via the keypad. Control via process

control is possible via either terminals or

Network depending on the settings in

O-50 Coasting Select to O-56 Preset Reference

Select.

[0]

Disable

Disables process control via PROFINET, and

enables process control via standard Network or

PROFINET IO-Supervisor.

[1]

*

Enable

cyclic

master

Enables process control via IO Controller, and

disables process control via standard Network or

PROFINET IO-Supervisor..

PB-53 Profibus Warning Word

Range:

Function:

0 N/A

*

[0 - 65535 N/A] This parameter displays PROFINET

communication warnings. Please refer

to the PROFINET Operating Instructions

for further information.

Read only

Parameters

PROFINET Operating Instruction

40