GE Industrial Solutions AF-650 GP PROFINET User Manual

Page 63

Advertising
background image

AF-650 GP & AF-600 FP

Bit (Hex)

Unit

diagnose

bit

PROFIBUS warning word

(PB-53 Profibus Warning Word)

00000001

160

Connection with DP-master is not ok

00000002

161

Unused

00000004

162

NDL (Network Data link Layer) is not

ok

00000008

163

Clear data command received

00000010

164

Actual value is not updated

00000020

165

Baudrate search

00000040

166

PROFIBUS ASIC is not transmitting

00000080

167

Initialising of PROFIBUS is not ok

00000100

152

Drive is tripped

00000200

153

Internal CAN error

00000400

154

Wrong configuration data from PLC

00000800

155

Wrong ID sent by PLC

00001000

156

Internal error occurred

00002000

157

Not configured

00004000

158

Timeout active

00008000

159

Warning 34 active

Table 10.18

AF-650 GP & AF-600 FP

Bit (Hex)

Comm. option STW (DR-84 Comm. Option STW)

00000001

parameters ok

00000002

configuration ok

00000004

clearmode active

00000008

baudrate search

00000010

waiting for parameterization

00000020

waiting for configuration

00000040

in data exchange

00000080

not used

00000100

not used

00000200

not used

00000400

not used

00000800

MCL2/1 connected

00001000

MCL2/2 connected

00002000

MCL2/3 connected

00004000

data transport active

00008000

not used

Table 10.19

NOTE

DR-84 Comm. Option STW is not part of extended
diagnostics.

Troubleshooting