2.1.7 Analog Input Commands (Acknowledged)

DRIVE Re-

sponse

Command

Subcom-

mand

Region

NPA Object no.

Attribute

No.

Attribute Message Type

Comments

ACK

1

-

1

0-23

1

Byte

Read Analog Input

Read Object Configuration at-

tribute associated with each

individual point

ACK

1

-

1

0-23

2

Byte

Read Analog Input

1)

Read Object Status attribute

associated with each

individual point

ACK

1

-

1

0-23

3

Float

Read Analog Input

2)

Read Analog Input Value at-

tribute associated with each

individual point

ACK

1

-

1

0-23

8

Float

Read Analog Input

Read Low Alarm attribute as-

sociated with each

individual point

ACK

1

-

1

0-23

9

Float

Read Analog Input

Read Low Warning attribute

associated with each

individual point

ACK

1

-

1

0-23

10

Float

Read Analog Input

Read High Warning attribute

associated with each

individual point

ACK

1

-

1

0-23

11

Float

Read Analog Input

Read High Alarm attribute as-

sociated with each

individual point

ACK

1

-

1

0-23

12

Float

Read Analog Input

Read Differential attribute as-

sociated with each

individual point

ACK

2

-

1

0-23

1

Byte

Write Analog Input

Write to Object Configuration

attribute associated with each

individual point

ACK

2

-

1

0-23

8

Float

Write Analog Input

Write to Low Alarm Limit attrib-

ute associated with each

individual point

ACK

2

-

1

0-23

9

Float

Write Analog Input

Write to Low Warning Limit at-

tribute associated with each

individual point

ACK

2

-

1

0-23

10

Float

Write Analog Input

Write to High Warning Limitat-

tribute associated with each

individual point

ACK

2

-

1

0-23

11

Float

Write Analog Input

Write to High Alarm Limit at-
tribute associated with each

individual point

ACK

2

-

1

0-23

12

Float

Write Analog Input

Write to Differential attribute

associated with each

individual point

ACK, no action

7

2

1

0-23

-

Float

Override Analog in-

puts

Analog inputs are "outputs"

from the frequency converter

and should not be written over

by the network controller

ACK, no action

7

3

1

0-23

-

-

Override Analog Re-

lease

Analog inputs are "outputs"

from the frequency converter

and should not be written over

by the network controller

ACK, no action

7

7

1

0-23

-

-

Write Analog Input

Attributes

Optional command for slave

devices. Only used for N2

commissioning purposes

Table 2.2: No Error code in this table.