Af-600 fp metasys, 11 binary input (bi) commands (acknowledged), 12 binary input (bi) commands (not acknowledged) – GE Industrial Solutions AF-600 FP Metasys User Manual

Page 14

Advertising
background image

2.1.11 Binary Input (BI) Commands (Acknowledged)

DRIVE

Response

Command

Subcom-

mand

Region

NPA Object no.

Attribute No.

Attribute Message Type

Comments

ACK

1

-

2

0-135

1

Byte

Read Binary In-

put

Read Object Configuration at-

tribute associated with each

individual point

ACK

1

-

2

0-135

2

Byte

Read Binary In-

put

Read Object Status attribute

associated with each individual

point

ACK

2

-

2

0-135

1

Byte

Write Binary In-

put

Write to Object Configuration at-

tribute associated with each

individual point

ACK, no action

7

2

2

0-135

-

Byte(0/1)

Override Binary

Input

Binary inputs are "outputs" from

the frequency converter and

should not be written over by the
network controller. (Status word,

Warnings, and Alarms)

ACK, no action

7

3

2

0-135

-

-

OverrideRelease Binary inputs are "outputs" from

the drive and should not be writ-
ten over by the network control-

ler. (Status word, Warnings and

Alarms)

ACK, no action

7

7

2

0-135

-

-

Write Binary In-

put

Optional command for slave de-
vices. Only Attributes used for N2
commissioning purposes. Not to

be implemented at this time

ACK, no action

7

8

2

0-135

-

-

Read Binary In-

put

Optional command for Attrib-

utes slave devices. Only used for
N2 commissioning purposes. Not

to be implemented at this time

2.1.12 Binary Input (BI) Commands (Not Acknowledged)

DRIVE

Response

Command

Region

NPA Object no.

Attribute No.

Attribute Message Type

Error Code

Comments

NAK

2

2

0-135

2

Byte

Write Binary In-

put

11

1

Object Status not writeable

NAK

2

2

0-135

3

Integer

Write Binary In-

put

11

1

Write Debouncing Value in msec at-

tribute associated with each

individual point.(JCI use only)

NAK

2

2

0-135

4

Inte-

ger32

Write Binary In-

put

11

1

Write Accumulator value attribute

associated with each individual

point (JCI use only)

Table 2.6: No Subcommand coloumn in this table.