2.1.10 Analog Output Commands (Not Acknowledged)

DRIVE

Response

Command

Region

NPA Object no. Attribute No.

Attribute Message Type

Error Code

Comments

0-2

1

3

0-2

4

Float

Read Analog Output

11

1

Read Low Linear Ranging Parameter

attribute associated with each

individual point. (JCI use only)

NAK

1

3

0-2

5

Float

Read Analog Output

11

1

Read High Linear Ranging Para-

meter attribute associated with

each individual point. (JCI use only)

NAK

2

3

0-2

2

Byte

Write Analog Out-

put

11

1

Object Status not writeable

NAK

2

3

0-2

3

Float

Write Analog Out-

put

11

1

Write to Current Value structure at-

tributes associated with each

individual point. (N2 does not sup-

port this, override function must be

used)

NAK

2

3

0-2

4

Float

Write Analog Out-

put

11

1

Write Debouncing Value in msec at-

tribute associated with each

individual point.(JCI use only)

NAK

2

3

0-2

5

Float

Write Analog Out-

put

11

1

Write Accumulator value attribute

associated with each individual

point. (JCI use only)

1)

Error code 11 is used because attributes are considered as fields/records in the point map database.

Table 2.5: No Subcommand coloumn in this table.

AF-600 FP Metasys

12