Af-600 fp metasys, 10 analog output commands (not acknowledged) – GE Industrial Solutions AF-600 FP Metasys User Manual
Page 13
2.1.10 Analog Output Commands (Not Acknowledged)
DRIVE
Response
Command
Region
NPA Object no. Attribute No.
Attribute Message Type
Error Code
Comments
0-2
1
3
0-2
4
Float
Read Analog Output
11
1
Read Low Linear Ranging Parameter
attribute associated with each
individual point. (JCI use only)
NAK
1
3
0-2
5
Float
Read Analog Output
11
1
Read High Linear Ranging Para-
meter attribute associated with
each individual point. (JCI use only)
NAK
2
3
0-2
2
Byte
Write Analog Out-
put
11
1
Object Status not writeable
NAK
2
3
0-2
3
Float
Write Analog Out-
put
11
1
Write to Current Value structure at-
tributes associated with each
individual point. (N2 does not sup-
port this, override function must be
used)
NAK
2
3
0-2
4
Float
Write Analog Out-
put
11
1
Write Debouncing Value in msec at-
tribute associated with each
individual point.(JCI use only)
NAK
2
3
0-2
5
Float
Write Analog Out-
put
11
1
Write Accumulator value attribute
associated with each individual
point. (JCI use only)
1)
Error code 11 is used because attributes are considered as fields/records in the point map database.
Table 2.5: No Subcommand coloumn in this table.
AF-600 FP Metasys
12
2