2 Instructions

2.1.1 Abbreviations and Definitions

Abbreviations and definitions

ACK

Acknowledge

ADF

Internal Floating Points

ADI

Internal Integers

AI

Analog Inputs

AO

Analog Outputs

BI

Binary Inputs

BO

Binary Outputs

COS

Change Of State

HPFB

High Performance Field Network

JCI

Johnson Controls Inc. developers of the METASYS N2 protocol

N2

METASYS N2

N2 master

A N2 master is either a PC with JCI software or a dedicated JCI controller

NAK

Not acknowledged

NPA

N2 Point Address (Each N2 Point Type has a address range from 0 to 255)

NPT

N2 Point Type

PAR

Parameter Number

2.1.2 Network Connection

Connect signal wires to terminal 68 (N+) and terminal 69 (N-) on main control board of the drive. If shielded cabling is used, connect one end of the shield to
terminal 61. This terminal is connected to ground via an internal RC link. It is highly recommended to use twisted-pair cables to reduce the differential mode
interference between the conductors

Torque Specifications:

4.5 in.lb. (0.5 Nm)

Control wire:

18 - 24 AWG, shielded, twisted pair

AF-600 FP Metasys

5