Example 3:

Over-ride analog output, speed (50%) change command:

Setting:

Device address

XX

Char1 command

7

Char1 subcommand

2

Char2 region

03

Char2 object number (NPA)

00

Char8 override value *

4E 00 00 00 override value = 50% speed (IEEE floating point, format)

Checksum

YY

Message code:
>XX7203004E000000<CR>

To calculate override value for speed: refer to Scaling of Network Reference
and Network Feedback. Issue an override release command through the
master to the device:

Example 4:

Bus stop, BO over-ride release command:

Setting:

Device address

XX

Char1 command

7

Char1 subcommand

2

Char2 region

04

Char2 object number (NPA)

04 (Start)

Char8 override value *

00 (Not active)

Checksum

Y

Message code:
>XX72040400YY <CR>

If the preceding commands were issued, the drive should have accelerated
to 50% after the speed reference was issued. After the override release, the
drive should have stopped.

2.2.2 Scaling of Bus Reference and Feedback

Reference/feedback

Scaling

Float

IEEX hex

20%

20 * 16384/100

3276.8

454C CCCD

50%

50 * 16384/100

8192

4600 0000

100%

100 * 16384/100

16384

4680 0000

200%

200 * 16384/100

32767

46FF FE00

-100%

-100 * 16384/100

-16384

C680 0000

-200%

-200 * 16384/100

-32768

C700 0000

Table 2.11: Reference/feedback values

The reference/feedback value is the percentage of the range of parameter F-52 and F-53. Values within the ranges 100% to 200% and -200% to -100% applies
only to the reference. The Float representation of the value 200% must be limited to maximum 32767 and minimum -32768.