2.1.9 Analog Output Commands (Acknowledged)

DRIVE

Response

Command

Sub

command

Region NPA Object no. Attribute No.

Attribute Message Type

Comments

ACK

1

-

3

0-2

1

Byte

Read Analog Output Read Object Configuration attrib-

ute associated with each

individual point

ACK

1

-

3

0-2

2

Byte

Read Analog Output Read Object Status attribute asso-

ciated with each individual point

ACK

0

9

-

-

-

-

Status update Mes-

sage

Slave device must respond with

device manufacturing model

number (Par. AN-21), days in ser-

vice (Par. AN-00) and device status

ACK

1

-

3

0-2

3

Float

Read Analog Output Read Current Value attribute asso-

ciated with each individual point

ACK

2

-

3

0-2

1

Byte

Write Analog Output Write to Object Configuration at-

tribute associated with each

individual point

ACK

7

2

3

0-2

-

Float

Override Analog Out-

put

Write to analog output current

value (frequency setpoint)

ACK

7

2

3

0-2

-

Float

Override Analog Out-

put

Write to analog output current

value (frequency setpoint)

ACK

7

3

3

0-2

-

-

Override Release

Set the current value, the value

that it was before the 1. Override

Command was issued

ACK, no action

7

7

3

0-2

-

-

Write Analog Output Optional command for slave devi-

ces. Only used for N2 Attributes

commissioning purposes. Not to

be implemented at this time

ACK, no action

7

8

3

0-2

-

-

Read Analog Output

Attributes

Optional command for no action

slave devices. Only used for N2

commissioning purposes. Not to

be implemented at this time

Table 2.4: No Error Code coloumn in this table.