3.1.2 Binary Inputs (BI)

NPT

NPA

UNIT

DESCRIPTION

RANGE

PAR. NUMBER

BI

0

-

Timers Status

0=OK , 1=Limit

DR-03

BI

1

-

Current Status

0=OK , 1=Limit

DR-03

BI

2

-

Voltage Status

0=OK , 1=Limit

DR-03

BI

3

-

Inverter Status

0=OK , 1 =Stall, Auto-start

DR-03

BI

4

-

Running Status

0=Not Running , 1=Running

DR-03

BI

5

-

Frequency Status

0=Out of Range , 1=In Range

DR-03

BI

6

-

Control Status

0=Local , 1= Bus

DR-03

BI

7

-

Reference Status

0=Not on Ref., 1=On Ref.

DR-03

BI

8

-

Warning Status

0=No Warning , 1= Warning

DR-03

BI

9

-

Tripped Status

0=No Trip , 1=Tripped

DR-03

BI

10

-

Drive Enabled Status

0=Not Enabled , 1=Enabled

DR-03

BI

11

-

Drive Ready Status

0=Not Ready , 1=Ready

DR-03

BI

12

-

Drive Controller Sta-

tus

0=Not Ready , 1=Ready

DR-03

BI

16

-

Auto tune suspicious

UNOM

0=OK , 1=Warning

DR-92

BI

17

-

Auto tune suspicious

INOM

0=OK , 1=Warning

DR-92

BI

18

-

Auto tune motor too

big

0=OK , 1=Warning

DR-92

BI

19

-

Auto tune motor too

small

0=OK, 1=Warning

DR-92

BI

20

-

Frequency low

0=OK , 1=Warning

DR-92

BI

21

-

Frequency high

0=OK , 1=Warning

DR-92

BI

22

-

Current low

0=OK , 1=Warning

DR-92

BI

23

-

Profibus warning

0=OK , 1=Warning

DR-92

BI

24

-

Output frequency

limited

0=OK , 1=Warning

DR-92

BI

25

-

Current high

0=OK , 1=Warning

DR-92

BI

26

-

Feedback low

0=OK , 1=Warning

DR-92

BI

27

-

Feedback high

0=OK , 1=Warning

DR-92

BI

28

-

Reference low

0=OK , 1=Warning

DR-92

BI

29

-

10 Volt low

0=OK, 1=Warning

DR-92

BI

30

-

Live zero error

0=OK , 1=Warning

DR-92

BI

31

-

Phase loss

0=OK , 1=Warning

DR-92

BI

32

-

DC link voltage high

0=OK , 1=Warning

DR-92

BI

33

-

DC link voltage low

0=OK , 1=Warning

DR-92

BI

34

-

DC link over voltage

0=OK , 1=Warning

DR-92

BI

35

-

DC link under voltage

0=OK , 1=Warning

DR-92

BI

36

-

Drive thermal

0=OK , 1=Warning

DR-92

BI

37

-

Motor thermal

0=OK, 1=Warning

DR-92

BI

38

-

Motor thermistor

0=OK , 1=Warning

DR-92

BI

39

-

Current limit

0=OK , 1=Warning

DR-92

BI

40

-

Over current

0=OK , 1=Warning

DR-92

BI

41

-

Standard bus time-

out

0=OK , 1=Warning

DR-92

BI

42

-

HPFB time-out

0=OK , 1=Warning

DR-92

BI

43

-

EEPROM error power

card

0=OK , 1=Warning

DR-92

Binary Inputs (BI), continued..