2.1.6 General Commands (Acknowledged)

DRIVE Response

Command

Subcommand

NPA Object

no.

Attribute Message Type

Error Code

Comments

ACK

0

4

-

Poll Message

No Acknowledge

-

The slave is to respond with any data points,

analog or binary I/O that have been flagged

for COS

ACK

0

5

-

Poll message

With Acknowledge

-

The slave is to respond with any data points,

analog or binary I/O that have been flagged

for COS

ACK

0

9

-

Status update Message

-

Slave device must respond with device man-

ufacturing model number (Par. AN-21), days in

service (Par. AN-00) and device status

ACK

F

-

-

Identify Device Type

-

Slave device responds with an identification

number of 10H to indicate non JCI device

ACK

0

0

-

Synch Time

-

The internal clock is syncronized by this com-

mand

ACK, no action

8

0

-

Upload

-

Optional, no support in the frequency

converter

ACK, no action

8

1

-

Upload

-

Optional, no support in the frequency

converter

ACK, no action

8

3

-

Upload Record

-

Optional, no support in the frequency

converter

ACK, no action

8

4

-

Upload Complete

-

Optional, no support in the frequency

converter

ACK, no action

9

0

-

Download

-

Optional, no support in the frequency

converter

ACK, no action

9

1

-

Download

-

Optional, no support in the frequency

converter

ACK, no action

9

3

-

Download

-

Record optional, no support in the frequency

converter

ACK, no action

9

4

-

Download Complete

-

Optional, no support in the frequency

converter

NAK

0

1

-

Read Memory

01

Slave device memory read based on memory

addresses

NAK

0

8

-

Warm Start

01

JCI use only