2.1.15 Internal Integers (ADI) Commands (Acknowledged)

DRIVE

Response

Command

Subcom-

mand

Region

NPA Object no.

Attribute No.

Attribute Message Type

Comments

ACK

1

-

6

0-254

1

Integer

Read Internal Pa-
rameter of object

type integer (16 bit)

Read Object Status associ-

ated with each individual

point

ACK

1

-

6

0-254

2

Integer

Read Internal Pa-
rameter of object

type integer (16bit)

Read Current Value attribute

associated with each

individual point

ACK

2

-

6

0-254

-

Integer

Write Internal Pa-

rameter of object

type integer (16bit)

Write to Current Value attrib-

ute associated with each

individual point

ACK

7

2

6

0-254

-

Integer

Override Internal

Parameter of ob-

ject type Integer

(16 bit)

Write to internal parameter

current value (set-up para-

meters for Drive)

ACK

7

3

6

0-254

-

-

Override Release Set the current value, the val-

ue that it was before the 1.

Override Command was

issued

Table 2.9: No Error Code coloumn in this table.

2.1.16 Internal Floating Point Commands (Acknowledged)

DRIVE

Response

Command

Subcom-

mand

Region

NPA Object no.

Attribute No.

Attribute Message Type

Comments

ACK

1

-

5

0-101

1

Byte

Read Internal Pa-
rameter of object

type float

Read Object Status associ-

ated with each individual

point

ACK

1

-

5

0-101

2

Float

Read Internal Pa-
rameter of object

type float

Read Current Value attrib-

ute associated with each

individual point

ACK

2

-

5

0-101

-

Float

Write Internal Pa-

rameter of object

type float

Write to Current Value

attribute associated with

each individual point

ACK

2

-

5

0-101

-

Float

Write Internal Pa-

rameter of object

type float

Write to Current Value

attribute associated with

each individual point

ACK

7

2

5

0-101

-

Float

Override Internal

Parameter of object

type float

Write to internal parameter

current value (set-up

parameters for Drive)

ACK

7

3

5

0-101

-

-

Override Release

Set the current value, the

value that it was before the

1. Override Command was

issued

Table 2.10: No Error Code coloumn in this table.